{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SDA068112R1","brand":"ABB","brandSlug":"abb","productSlug":"1SDA068112R1","canonicalUrl":"https://aoctrl.com/abb/1SDA068112R1","factsUrl":"https://aoctrl.com/api/mcp/products/1SDA068112R1","rawCanonicalId":null},"summary":{"shortDescription":"ABB 1SDA068112R1, XT4N 160 MA 10 motor protection circuit breaker, 3-pole, In 10 A, Iu 160 A frame, adjustable magnetic-only trip, 690 V, 50/60 Hz.","salesMarkdown":"## Motor protection for the grease-and-grit route The ABB 1SDA068112R1 is an XT4N 160 frame motor protection circuit breaker with a magnetic-only (MA) trip unit, set for 10 A full-load current. The adjustable instantaneous magnetic trip range (Im) goes from 50 to 100 A, so it handles motor inrush without nuisance tripping on start-up. Rated for 690 V at 50/60 Hz, this is a three-pole unit built for protecting induction motors in industrial environments — think pumps, conveyors, and fans out on the plant floor where heat, dust, and vibration are the real test. The 160 A frame rating (Iu) means the physical breaker shell and contacts are sized for a 160 A maximum; you're using a small chunk of that capacity here, which gives thermal headroom in the enclosure. The MA trip unit means no thermal overload — it's strictly magnetic (short-circuit and start-up protection), so you must pair this breaker with a separate overload relay for running protection. The adjustable Im range (50 to 100 A) lets you dial in the magnetic pickup to ride through your motor's locked-rotor current without tripping, typically set at 8-12x the motor FLA for standard induction motors.","metaTitle":"ABB 1SDA068112R1 XT4N 160 MA 10 Motor Protection Circuit Bre","metaDescription":"ABB XT4N 160 motor protection circuit breaker, 10 A rated current, MA trip unit with adjustable magnetic release (Im=50...100 A). 690 V, 50/60 Hz, 3-pole. Active production. Source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["MCCB up to 100A"],"specifications":{"In":"10","Iu":"160","Size":"XT4","Type":"XT4N 160 MA 10 Im=50...100 3p F F","title":"1SDA068112R1","Weight":"2.1 Kg","Trip units":"MA","Product No.":"1SDA068112R1","description":"Motor Protection Circuit Breakers","Product Type":"Motor Protection Circuit Breakers","Number of Poles":"3 poles","Shipping Weight":"4 Kg","lifecycle_stage":"current","Dimensions (LxWxH)":"8.25cm x 10.5cm x 16cm","Rated Current (In)":"10 A","Rated Voltage (Ur)":"690 V","Estimated Lead Time":"2 - 4 weeks.","Rated Frequency (f)":"50 / 60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$433.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/869265304e2a91d543387a4121111429.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What does the MA trip unit mean for application?","answer":"The MA trip unit is magnetic-only — it provides short-circuit and instantaneous overcurrent protection but no thermal overload. You must pair this breaker with a separate thermal overload relay (e.g., ABB TA or TF series) to protect the motor from running overloads."},{"question":"What is the adjustable magnetic release range?","answer":"The adjustable instantaneous magnetic release (Im) ranges from 50 to 100 A, allowing you to set the short-circuit pickup level to suit the motor's starting inrush without nuisance tripping."},{"question":"What voltage and frequency is this breaker rated for?","answer":"Rated voltage is 690 V AC, and it handles both 50 and 60 Hz supplies."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SDA068112R1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SDA068112R1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}