{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SDA068117R1","brand":"ABB","brandSlug":"abb","productSlug":"1SDA068117R1","canonicalUrl":"https://aoctrl.com/abb/1SDA068117R1","factsUrl":"https://aoctrl.com/api/mcp/products/1SDA068117R1","rawCanonicalId":null},"summary":{"shortDescription":"ABB XT4N 160 MA 80 motor protection circuit breaker, 1SDA068117R1, 80 A In, adjustable magnetic trip 400–800 A, 3-pole, 690 V.","salesMarkdown":"## Motor protection with adjustable magnetic trip The ABB 1SDA068117R1 is a motor protection circuit breaker from the XT4N series, rated at 80 A continuous and featuring an adjustable magnetic trip unit with a range of 400–800 A to handle motor starting inrush. The MA trip unit (magnetic-only) eliminates nuisance tripping during startup — the core reason you spec this over a thermal-magnetic breaker for motor circuits. Frame rating Iu of 160 A gives the XT4 short-circuit withstand headroom typical of this frame class. Three-pole design at 690 V rated voltage suits standard 400 V or 690 V motor feeders. The adjustable trip range means you dial in the magnetic pick-up between 400 and 800 A, covering motors with full-load currents up to the 80 A In limit.","metaTitle":"ABB 1SDA068117R1 XT4N 160 MA 80, Motor Protection CB 80A","metaDescription":"ABB 1SDA068117R1 XT4N 160 MA 80 motor protection breaker, 80 A rated, adjustable magnetic trip 400–800 A, 3-pole, 690 V, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"In":"80","Iu":"160","Size":"XT4","Type":"XT4N 160 MA 80 Im=400...800 3p F F","Weight":"2.1 Kg","Trip units":"MA","Product No.":"1SDA068117R1","Manufacturer":"ABB","Product Type":"Motor Protection Circuit Breakers","Number of Poles":"3 poles","Shipping Weight":"4 Kg","lifecycle_stage":"current","Dimensions (LxWxH)":"8.25cm x 10.5cm x 16cm","Rated Current (In)":"80 A","Rated Voltage (Ur)":"690 V","Estimated Lead Time":"2 - 4 weeks.","Rated Frequency (f)":"50 / 60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$433.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/eac395844401f9790c347b4f702449a5.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/1SDA068117R1/alternatives.json"},"ai":{"faq":[{"question":"What is the rated continuous current (In)?","answer":"The rated current In is 80 A."},{"question":"What is the adjustable magnetic trip range?","answer":"The magnetic trip unit is adjustable from 400 A to 800 A (Im)."},{"question":"What is the typical lead time for ordering?","answer":"Estimated lead time is 2–4 weeks when quoted to order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SDA068117R1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SDA068117R1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}