{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SDA068160R1","brand":"ABB","brandSlug":"abb","productSlug":"1SDA068160R1","canonicalUrl":"https://aoctrl.com/abb/1SDA068160R1","factsUrl":"https://aoctrl.com/api/mcp/products/1SDA068160R1","rawCanonicalId":null},"summary":{"shortDescription":"ABB XT4N 160 molded case circuit breaker, Ekip LSIG trip unit, In=100 A, Iu=160 A frame, 4-pole, 690 V, 50/60 Hz, fixed front terminals.","salesMarkdown":"## Frame and trip unit — what the type code tells you The 1SDA068160R1: The XT4N 160 frame (size XT4) is the mechanical envelope rated Iu=160 A — this is the maximum current the breaker's thermal-magnetic structure can carry before the trip unit takes over. The Ekip LSIG trip unit is an electronic release with L (long-time), S (short-time), I (instantaneous), and G (ground-fault) protection curves, all field-adjustable via the front keypad or Ekip Connect software. Rated current In=100 A means the breaker is factory-set to protect a 100 A continuous load. The 4-pole configuration switches three phases plus neutral, common in TN or TT distribution panels where the neutral needs overcurrent protection. ## Voltage and frequency — system compatibility Rated voltage Ur=690 V AC covers 400 V and 480 V distribution as well as 690 V industrial networks. Rated frequency 50/60 Hz means the breaker is at home on either mains standard — no derating needed between the two. ## Lifecycle and sourcing — active, quoted to order Sourced through authorized distribution against the BOM quantity. Availability and current pricing confirmed at RFQ; typical lead time is 2–4 weeks for production quantities.","metaTitle":"ABB 1SDA068160R1 XT4N 160 Ekip LSIG, 100 A, 4-pole","metaDescription":"ABB 1SDA068160R1 molded case circuit breaker, XT4N 160 frame, Ekip LSIG trip unit, In=100 A, 4-pole, 690 V, 50/60 Hz. Active production, sourced per RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["MCCB up to 100A"],"specifications":{"In":"100","Iu":"160","Size":"XT4","Type":"XT4N 160 Ekip LSIG In=100A 4p F F","title":"1SDA068160R1","Weight":"3.1 Kg","Trip units":"Ekip LSIG","Product No.":"1SDA068160R1","description":"Distribution Circuit Breakers","Product Type":"Distribution Circuit Breakers","Number of Poles":"4 poles","Shipping Weight":"5 Kg","lifecycle_stage":"current","Dimensions (LxWxH)":"8.25cm x 14cm x 16cm","Rated Current (In)":"100 A","Rated Voltage (Ur)":"690 V","Estimated Lead Time":"2 - 4 weeks.","Rated Frequency (f)":"50 / 60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,222.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/036c56a5759a46180410fa46d9517e6a.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the lead time for 1SDA068160R1?","answer":"Typical lead time is 2–4 weeks for production quantities. Availability is confirmed at RFQ against the specific BOM quantity."},{"question":"What does the Ekip LSIG trip unit protect against?","answer":"Ekip LSIG provides four protection functions: L (long-time overload), S (short-time delay), I (instantaneous short-circuit), and G (ground-fault). All are adjustable via the front keypad or software."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SDA068160R1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SDA068160R1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}