{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SDA068169R1","brand":"ABB","brandSlug":"abb","productSlug":"1SDA068169R1","canonicalUrl":"https://aoctrl.com/abb/1SDA068169R1","factsUrl":"https://aoctrl.com/api/mcp/products/1SDA068169R1","rawCanonicalId":null},"summary":{"shortDescription":"ABB XT2S 160 breaking part, 4-pole, Iu 160 A, Icu 50 kA at 415 V AC, 690 V rated, 50/60 Hz, DIN-rail mount.","salesMarkdown":"The ABB 1SDA068169R1 is an XT2S 160 breaking part, 4-pole, rated Iu 160 A continuous. It is not a complete MCCB — it is the interrupter mechanism without a trip unit, functioning as a switch-disconnector or as the base for a field-installed trip block. ## Rated voltage and frequency — what the 690 V and 50/60 Hz mean on the line Rated voltage Ur 690 V AC covers standard 400/480 V systems with 50% headroom, and also suits 690 V mining, marine, or industrial installations where the line-to-line voltage is higher.","metaTitle":"ABB 1SDA068169R1 XT2S 160 Breaking Part, 4P, Iu 160 A","metaDescription":"ABB 1SDA068169R1 XT2S 160 breaking part, 4-pole, Iu 160 A, Icu 50 kA at 415 V. Active production. Sourced to order against RFQ. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Iu":"160","Size":"XT2","Type":"XT2S 160 BREAKING PART 4p F F","title":"1SDA068169R1","Weight":"1.2 Kg","Icu (415 V)":"50","Product No.":"1SDA068169R1","description":"Breaking Part","Product Type":"Breaking Part","Number of Poles":"4 poles","Shipping Weight":"2.5 Kg","lifecycle_stage":"current","Dimensions (LxWxH)":"8.25cm x 12cm x 13cm","Rated Voltage (Ur)":"690 V","Estimated Lead Time":"2 - 4 weeks.","Rated Frequency (f)":"50 / 60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$179.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/76b6b29fb41f12adea793f8d235b2f5d.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the Iu rating of 1SDA068169R1?","answer":"The Iu (continuous rated current) is 160 A. This is the current the breaking part is designed to carry continuously without exceeding temperature rise limits, and is the value the thermal-magnetic trip unit would be sized to if one were installed."},{"question":"What compliance documentation does ABB provide for 1SDA068169R1?","answer":"ABB provides standard compliance documentation including RoHS and REACH declarations, and the part carries IEC and UL certifications as standard for the XT2 series. Specific certificates are available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SDA068169R1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SDA068169R1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}