{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SDA068171R1","brand":"ABB","brandSlug":"abb","productSlug":"1SDA068171R1","canonicalUrl":"https://aoctrl.com/abb/1SDA068171R1","factsUrl":"https://aoctrl.com/api/mcp/products/1SDA068171R1","rawCanonicalId":null},"summary":{"shortDescription":"ABB XT2L 160 breaking part, 4-pole, Iu 160 A, Icu 120 kA at 415 V, 690 V rated, 50/60 Hz, current production.","salesMarkdown":"## What this breaking part is and isn't The 1SDA068171R1 is the switching mechanism only — the 'breaking part' of an ABB XT2L 160 MCCB. It mates with a separate base and trip unit to form a complete molded case circuit breaker. If you're ordering this for a panel build, confirm you already have the matching base; this part alone won't mount to the bus. Rated Iu 160 A continuous current on the XT2 frame, with a fault-breaking capacity Icu of 120 kA at 415 V AC. That's enough clearing capacity for most industrial main feeders and large subfeeders — the 120 kA rating means it can safely interrupt a bolted fault up to that level without venting or cascading upstream. ## Panel fit and electrical specs Four-pole configuration handles three-phase plus neutral switching — common for TN-S or TN-C-S systems where the neutral needs isolation. Rated voltage 690 V AC gives headroom above the standard 400/480 V distribution levels. Frequency rated 50/60 Hz, so it's universal for global installations without derating. ## Sourcing and lifecycle Sourced and quoted to order against your BOM quantity. No minimum order quantity beyond what the supplier requires for this ABB line.","metaTitle":"ABB 1SDA068171R1 XT2L 160 Breaking Part, 4p, Iu 160 A","metaDescription":"ABB 1SDA068171R1 XT2L 160 breaking part, 4-pole, Iu 160 A, Icu 120 kA at 415 V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Iu":"160","Size":"XT2","Type":"XT2L 160 BREAKING PART 4p F F","title":"1SDA068171R1","Weight":"1.2 Kg","Icu (415 V)":"120","Product No.":"1SDA068171R1","description":"Breaking Part","Product Type":"Breaking Part","Number of Poles":"4 poles","Shipping Weight":"2.5 Kg","lifecycle_stage":"current","Dimensions (LxWxH)":"8.25cm x 12cm x 13cm","Rated Voltage (Ur)":"690 V","Estimated Lead Time":"2 - 4 weeks.","Rated Frequency (f)":"50 / 60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$248.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/82bec2b2cc66e153ea9f3ee12cf810c5.pdf","sourceUrl":null},"ai":{"faq":[{"question":"How do I get pricing and availability for 1SDA068171R1?","answer":"Submit an RFQ through this listing. Lead time is typically 2-4 weeks for current-production ABB parts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SDA068171R1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SDA068171R1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}