{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA894013R7000","brand":"ABB","brandSlug":"abb","productSlug":"1SFA894013R7000","canonicalUrl":"https://aoctrl.com/abb/1SFA894013R7000","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA894013R7000","rawCanonicalId":null},"summary":{"shortDescription":"ABB PST250 softstarter, 1SFA894013R7000, 250 A rated operational current (inline), 132 kW at 400 V, built-in electronic overload protection, 0–120 s ramp time.","salesMarkdown":"The ABB 1SFA894013R7000 is a PST250-series softstarter rated for 250 A in-line connection (Ie) and 430 A inside-delta, delivering 132 kW at 400 V in-line or 220 kW at 400 V inside-delta. It carries a built-in electronic overload with a current-limit function adjustable from 1.5 to 7 times Ie, so the overload curve is integral — no separate external relay needed on the line side. The ramp time spans 0 to 120 seconds, with initial voltage during start settable 30–70 % and a step-down special ramp from 100 down to 30 %, giving you control over both acceleration and deceleration profiles for pump, fan, or conveyor starts. ## Control and feedback Control supply voltage is 100–250 V AC; a separate 24 V DC control circuit is available for PLC-level logic. The unit provides dedicated run, fault, bypass, and overload signal relays — four discrete dry contacts for status feedback to the controller without adding interface modules. Communication is via a standard FieldBusPlug, meaning it accepts the common ABB fieldbus adapter for PROFIBUS, DeviceNet, or Modbus RTU without a separate gateway. Analog output is 0–10 V, usable for speed or current follow. Main circuit terminals are bars with a 10.2 mm hole — expect bus-bar or cable-lug connections, not spring-clamp. Control-circuit tightening torque is 0.5 N·m. The main terminals carry IP00 protection per IEC 60529, so the unit is intended for enclosure mounting where the cabinet provides the environmental seal. Ambient operating range is 0 to +50 °C, with a 115 % service factor — it can sustain 115 % of rated current for short periods without tripping, useful for high-inertia loads.","metaTitle":"ABB 1SFA894013R7000 PST250 Softstarter, 250 A Inline, 132 kW","metaDescription":"ABB PST250 softstarter 1SFA894013R7000, 250 A inline / 430 A inside-delta, 132 kW at 400 V. Built-in electronic overload, 0-120 s ramp. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Soft Starters"],"specifications":{"Ramp Time":"0 ... 120 second [unit of time]","Communication":"FiledBusPlug(Standard)","Terminal Type":"Main Circuit: Bars","Analog Outputs":"0...10 volts","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PST250","Tightening Torque":"Control Circuit 0.5 N·m","Fault Signal Relay":"Yes","Overload Protection":"Build-in electronic overload protection","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"Yes","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00","Overload Signal Relay":"Yes","Current Limit Function":"1.5 ... 7xIe","Ambient Air Temperature":"Operation 0 ... +50 °C","Rated Operational Voltage":"Main Circuit 208 ... 600 V AC","Service Factor Percentage":"115 %","Object Classification Code":"Q","Initial Voltage During Start":"30 ... 70 %","Signal Indication Fault (LED)":"Red","Integrated Electronic Overload":"Yes","Step Down Voltage Special Ramp":"100 ... 30 %","Connecting Capacity Main Circuit":"Hole Diameter 10.2 mm","Material Compliance/WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 250 V AC","Connecting Capacity Supply Circuit":"Rigid 1 x 2.5","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"DC Operation 24 V","Signal Indication Protection (LED)":"Yellow","Switch for Inside Delta Connection":"Yes","Connecting Capacity Control Circuit":"Rigid 1 x 2.5 mm²","Material Compliance/RoHS Information":"No declaration needed","Popular Downloads/Instructions and Manuals":"1SFC132003M0201","Starting Capacity at Maximum Rated Current Ie":"3xIe for 15s","Rated Operational Power - In-Line Connection (Pe)":"(400 V) 132 kW","Rated Operational Power - Inside Delta Connection":"at 400 V 220 kW","Popular Downloads/Data Sheet, Technical Information":"1SFC132005C0201","Rated Operational Current - In-Line Connection (Ie)":"250 A","Rated Operational Current - Inside Delta Connection":"430 A","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa894013r7000","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA894013R7000/alternatives.json"},"ai":{"faq":[{"question":"What is the ramp time range on the 1SFA894013R7000?","answer":"The ramp time is adjustable from 0 to 120 seconds, with initial voltage during start settable 30–70 % and a step-down special ramp from 100 down to 30 %."},{"question":"What communication interface does this PST250 use?","answer":"It uses a standard FieldBusPlug, which accepts ABB's fieldbus adapter modules for PROFIBUS, DeviceNet, Modbus RTU, or other protocols without a separate gateway."},{"question":"Where can I buy the 1SFA894013R7000?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA894013R7000","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA894013R7000 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}