{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA895015R7000","brand":"ABB","brandSlug":"abb","productSlug":"1SFA895015R7000","canonicalUrl":"https://aoctrl.com/abb/1SFA895015R7000","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA895015R7000","rawCanonicalId":null},"summary":{"shortDescription":"ABB PSTB370 softstarter, order code 1SFA895015R7000, 370 A rated operational current in-line connection, 640 A inside-delta, 200 kW / 355 kW at 400 V, built-in electronic overload protection, ramp time 0–120 s, FieldBusPlug communication.","salesMarkdown":"The inside-delta connection (640 A) applies when the softstarter is wired in the delta legs of a six-lead motor, which reduces the current through each phase device; the 355 kW figure at 400 V tells you the motor power it can start in that configuration. The ramp time from 0 to 120 seconds gives you a wide window to tune acceleration for soft-start applications like conveyors or pumps, avoiding mechanical shock. ## Deployment context This is a panel-mount softstarter — main circuit terminals are bars (hole diameter 10.5 mm), control circuit terminals accept 1 x 2.5 mm² rigid, tightened to 0.5 N·m. The IP00 main terminals mean it lives inside an enclosure; plan for adequate clearance and cooling, especially at the 640 A delta rating where heat dissipation matters.","metaTitle":"ABB PSTB370 1SFA895015R7000 Softstarter, 370 A In-Line, 355","metaDescription":"ABB PSTB370 softstarter, 370 A in-line (Ie), 640 A inside-delta, 200 kW / 355 kW at 400 V. Built-in electronic overload, ramp 0–120 s, FieldBusPlug. Current lifecycle, sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Soft Starters"],"specifications":{"Ramp Time":"0 ... 120 second [unit of time]","Communication":"FiledBusPlug(Standard)","Terminal Type":"Main Circuit: Bars","Analog Outputs":"0...10 volts","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PSTB370","Tightening Torque":"Control Circuit 0.5 N·m","Fault Signal Relay":"Yes","Overload Protection":"Build-in electronic overload protection","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"Yes","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00","Overload Signal Relay":"Yes","Current Limit Function":"1.5 ... 7xIe","Ambient Air Temperature":"Operation 0 ... +50 °C","Rated Operational Voltage":"Main Circuit 400 ... 690 V AC","Service Factor Percentage":"115 %","Object Classification Code":"Q","Initial Voltage During Start":"30 ... 70 %","Signal Indication Fault (LED)":"Red","Integrated Electronic Overload":"Yes","Step Down Voltage Special Ramp":"100 ... 30 %","Connecting Capacity Main Circuit":"Hole Diameter 10.5 mm","Material Compliance/WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 250 V AC","Connecting Capacity Supply Circuit":"Rigid 1 x 2.5","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"DC Operation 24 V","Signal Indication Protection (LED)":"Yellow","Switch for Inside Delta Connection":"Yes","Connecting Capacity Control Circuit":"Rigid 1 x 2.5 mm²","Material Compliance/RoHS Information":"No declaration needed","Popular Downloads/Instructions and Manuals":"1SFC132003M0201","Starting Capacity at Maximum Rated Current Ie":"3xIe for 15s","Rated Operational Power - In-Line Connection (Pe)":"(400 V) 200 kW","Rated Operational Power - Inside Delta Connection":"at 400 V 355 kW","Popular Downloads/Data Sheet, Technical Information":"1SFC132005C0201","Rated Operational Current - In-Line Connection (Ie)":"370 A","Rated Operational Current - Inside Delta Connection":"640 A","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa895015r7000","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA895015R7000/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 1SFA895015R7000 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the ramp time range on the PSTB370?","answer":"The ramp time is adjustable from 0 to 120 seconds, giving you control over acceleration for soft-start applications."},{"question":"What communication interface does 1SFA895015R7000 use?","answer":"It uses a standard FieldBusPlug for communication — a modular connector interface for fieldbus integration."},{"question":"What compliance documentation is available for this softstarter?","answer":"The part carries no RoHS declaration needed per the material compliance data, and is classified as B2B (Business To Business) under WEEE. Refer to the instruction manual (1SFC132003M0201) and datasheet (1SFC132005C0201) for full compliance details."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA895015R7000","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA895015R7000 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}