{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA896207R7000","brand":"ABB","brandSlug":"abb","productSlug":"1SFA896207R7000","canonicalUrl":"https://aoctrl.com/abb/1SFA896207R7000","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA896207R7000","rawCanonicalId":null},"summary":{"shortDescription":"ABB, PSRC16 series, Soft start with voltage ramp, 1SFA896207R7000, 208-600 V AC, 4xIe for 6s starting capacity, IP20 screw terminals.","salesMarkdown":"## Soft start with voltage ramp, fixed ramp time The ABB 1SFA896207R7000 is a PSRC16 soft starter that applies a voltage ramp to limit inrush during motor start. Ramp time is a fixed setting — no field adjustment — so the part is sized for a specific load profile and swapped rather than tuned. Starting capacity is 4xIe for 6 seconds, which covers standard induction-motor acceleration on pumps, fans, and small conveyors without a bypass contactor. Control supply is 100-240 V AC; the control circuit can also take 24 V DC for PLC-driven panels. ## Terminals, protection, and integration Main circuit terminals accept rigid 0.75 to 2.5 mm² wire; control-circuit torque is 1 N·m. Screw terminals throughout — no spring-cage option on this variant. The enclosure is IP20 at the main terminals per IEC 60529 and IEC 60947-1, so it mounts inside a panel with a door or cover; not for standalone washdown duty. Overload protection is recommended via an external MS132 manual motor starter in the 10.00 to 16.00 A range — the PSRC16 does not integrate electronic overload. A run signal relay is present; fault, bypass, and overload signal relays are not. Communication is optional through a FiledBusPlug accessory.","metaTitle":"ABB PSRC16 Soft Starter 1SFA896207R7000, 4xIe for 6s","metaDescription":"ABB PSRC16 soft starter 1SFA896207R7000 with voltage ramp, 208-600 V AC, 4xIe starting capacity, IP20 terminals. Current production, available to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Function":"Soft start with voltage ramp","Ramp Time":"Fixed setting","Communication":"FiledBusPlug(Optional)","Terminal Type":"Screw Terminals","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PSRC16","Tightening Torque":"Control Circuit 1 N·m","Fault Signal Relay":"No","Overload Protection":"Recommended MS132 10.00 ... 16.00","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"No","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20","Overload Signal Relay":"No","Current Limit Function":"No","Ambient Air Temperature":"Operation -25 ... +60 °C","Rated Operational Voltage":"208 ... 600 V AC","Service Factor Percentage":"100 %","Object Classification Code":"Q","Initial Voltage During Start":"Fixed setting","Popular Downloads/EPLAN Data":"9AAC172770_EPLAN","Integrated Electronic Overload":"No","Step Down Voltage Special Ramp":"Fixed setting","Connecting Capacity Main Circuit":"Rigid 1 x 0.75 ... 2.5 mm²","Material Compliance/WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 240 V AC","Signal Indication Running R (LED)":"Green","Connecting Capacity Supply Circuit":"Rigid 2 x 0.75 ... 1.5","IDEA Granular Category Code (IGCC)":"4740 >> Soft starter","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"24 V DC","Switch for Inside Delta Connection":"No","Material Compliance/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Signal Indication Ramping Up/Down (LED)":"Green","Popular Downloads/CAD Dimensional Drawing":"2CDC001079B0201","Technical UL/CSA/Horsepower Rating UL/CSA":"(200 ... 208 V AC) Three Phase 3 Hp","Technical UL/CSA/Tightening Torque UL/CSA":"Control Circuit 8.9 in·lb","Popular Downloads/Instructions and Manuals":"1SFC132041M0001","Signal Indication Completed Start Ramp (LED)":"Green","Starting Capacity at Maximum Rated Current Ie":"4xIe for 6s","Rated Operational Power - In-Line Connection (Pe)":"(230 V) 4 kW","Technical UL/CSA/Maximum Operating Voltage UL/CSA":"Main Circuit 600 V","Popular Downloads/Data Sheet, Technical Information":"1SFC132012C0201","Popular Downloads/Instructions and Manuals (Part 3)":"1SFC132060M0201","Rated Operational Current - In-Line Connection (Ie)":"16 A","Material Compliance/Toxic Substances Control Act - TSCA":"2CMT2023-006524","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa896207r7000","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA896207R7000/alternatives.json"},"ai":{"faq":[{"question":"What is the starting capacity of this soft starter?","answer":"Starting capacity is 4xIe for 6 seconds, suitable for standard induction motor acceleration."},{"question":"What compliance documentation is available for 1SFA896207R7000?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. WEEE category B2B small equipment. UL/CSA rated at 3 Hp at 200-208 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA896207R7000","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA896207R7000 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}