{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA897112R7001","brand":"ABB","brandSlug":"abb","productSlug":"1SFA897112R7001","canonicalUrl":"https://aoctrl.com/abb/1SFA897112R7001","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA897112R7001","rawCanonicalId":null},"summary":{"shortDescription":"ABB PSE210 soft starter, 1SFA897112R7001, soft start with torque control, 208...600 V AC, 50/60 Hz, Modbus-RTU, 0...30 s ramp, built-in electronic overload protection.","salesMarkdown":"## What this soft starter does on the line The ABB PSE210 1SFA897112R7001 is a soft starter with torque control, meaning it ramps voltage to the motor during start rather than slamming it across the line. That ramp time is adjustable from 0 to 30 seconds, and the initial voltage during start can be set between 30 and 70 percent of line voltage. For a pump or conveyor that needs a gentle acceleration curve, this is the parameter that sets the jerk limit. Communication is Modbus-RTU over the control circuit, which runs on 24 V DC. The main circuit terminals are bars — hole diameter 8.5 mm — sized for the 208 to 600 V AC range it operates on. The control supply voltage is separate, 100 to 250 V AC, so the logic stays live even when the motor circuit is off. Built-in electronic overload protection covers locked rotor, current underload, and EOL detection. The current limit function is adjustable from 1.5 to 7 times the motor full-load current, which gives you the headroom to handle high-inertia starts without tripping on the inrush. Main terminals are rated IP00 per IEC 60529 and IEC 60947-1 — that means no enclosure protection at the terminals themselves, so this unit lives inside a panel or cabinet that provides the overall IP rating. The control circuit connects via rigid 1 x 2.5 mm² wire, torqued to 0.5 N·m. The supply circuit takes the same wire size. Three signal relays are onboard: run, fault, and bypass — all standard for a soft starter that needs to tell the PLC what it's doing.","metaTitle":"ABB PSE210 Soft Starter 1SFA897112R7001, 208-600V AC, Modbus","metaDescription":"ABB PSE210 soft starter with torque control, 208-600V AC, Modbus-RTU, 0-30s ramp, built-in overload protection. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Function":"Soft start with torque control","Ramp Time":"0 ... 30 second [unit of time]","Communication":"Modbus-RTU","Terminal Type":"Main Circuit: Bars","Analog Outputs":"4...20 mA","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PSE210","Tightening Torque":"Control Circuit 0.5 N·m","Fault Signal Relay":"Yes","Overload Protection":"Built-in electronic overload protection","Protection Function":"Electronic overload protection, EOL; Locked rotor protection; Current underload protection","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"Yes","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00","Overload Signal Relay":"Yes","Current Limit Function":"1.5 ... 7xIe","Ambient Air Temperature":"Operation -25 ... +60 °C","Rated Operational Voltage":"208 ... 600 V AC","Service Factor Percentage":"100 %","Object Classification Code":"Q","Initial Voltage During Start":"30 ... 70 %","Popular Downloads/EPLAN Data":"9AAC170222_EPLAN","Signal Indication Fault (LED)":"Red","Integrated Electronic Overload":"Yes","Step Down Voltage Special Ramp":"No %","Connecting Capacity Main Circuit":"Hole Diameter 8.5 mm","Material Compliance/WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 250 V AC","Signal Indication Running R (LED)":"Green","Connecting Capacity Supply Circuit":"Rigid 1 x 2.5","IDEA Granular Category Code (IGCC)":"4740 >> Soft starter","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"24 V DC","Signal Indication Protection (LED)":"Yellow","Switch for Inside Delta Connection":"No","Connecting Capacity Control Circuit":"Rigid 1 x 2.5 mm²","Material Compliance/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Signal Indication Ramping Up/Down (LED)":"Green","Popular Downloads/CAD Dimensional Drawing":"2CDC001079B0201","Technical UL/CSA/Horsepower Rating UL/CSA":"(200 ... 208 V AC) Three Phase 60 Hp","Technical UL/CSA/Tightening Torque UL/CSA":"Control Circuit 4.4 in·lb","Popular Downloads/Instructions and Manuals":"1SFC132427M0201","Signal Indication Completed Start Ramp (LED)":"Green","Starting Capacity at Maximum Rated Current Ie":"4xIe for 10s","Rated Operational Power - In-Line Connection (Pe)":"(230 V) 59 kW","Technical UL/CSA/Maximum Operating Voltage UL/CSA":"Main Circuit 600 V","Popular Downloads/Data Sheet, Technical Information":"1SFC132012C0201","Popular Downloads/Instructions and Manuals (Part 2)":"1SFC132057M0201","Popular Downloads/Instructions and Manuals (Part 3)":"1SFC132060M0201","Rated Operational Current - In-Line Connection (Ie)":"210 A","Material Compliance/Toxic Substances Control Act - TSCA":"2CMT2023-006524","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa897112r7001","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA897112R7001/alternatives.json"},"ai":{"faq":[{"question":"What is the ramp time range on this soft starter?","answer":"The ramp time is adjustable from 0 to 30 seconds, and the initial voltage during start can be set between 30 and 70 percent of the line voltage."},{"question":"What communication protocol does this unit support?","answer":"It uses Modbus-RTU over the 24 V DC control circuit."},{"question":"Where can I buy 1SFA897112R7001?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"What protection functions are built in?","answer":"It includes electronic overload protection, locked rotor protection, current underload protection, and EOL detection. The current limit is adjustable from 1.5 to 7 times the motor full-load current."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA897112R7001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA897112R7001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}