{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA897114R7001","brand":"ABB","brandSlug":"abb","productSlug":"1SFA897114R7001","canonicalUrl":"https://aoctrl.com/abb/1SFA897114R7001","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA897114R7001","rawCanonicalId":null},"summary":{"shortDescription":"ABB PSE300 soft starter, order code 1SFA897114R7001, soft start with torque control, 208-600 V AC, Modbus-RTU, built-in electronic overload protection.","salesMarkdown":"The ABB PSE300 1SFA897114R7001 is a soft starter with torque control, built for three-phase induction motors on 208–600 V AC lines. Ramp time is adjustable 0–30 s, with initial voltage set 30–70 % and current limit 1.5–7× Ie. Communication rides Modbus-RTU, so it drops into a PLC network without a separate gateway. Control supply is 100–250 V AC; the separate 24 V DC control circuit handles the logic side. Main circuit terminals are bars with an 8.5 mm hole — expect lug-type connections. Control circuit terminals accept rigid 1 x 2.5 mm² wire; tighten to 0.5 N·m. Main terminals are IP00 — the unit lives inside an enclosure. Built-in electronic overload protection covers locked rotor, current underload, and EOL. Three signal relays (run, fault, bypass, overload) give discrete feedback to the controller. Analog output is 4–20 mA for current or torque monitoring. Status LEDs: green for running/ramping, red for fault, yellow for protection trip.","metaTitle":"ABB PSE300 Soft Starter 1SFA897114R7001, 208-600 VAC, Modbus","metaDescription":"ABB PSE300 soft starter with torque control, 208-600 VAC, Modbus-RTU, built-in overload protection. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Function":"Soft start with torque control","Ramp Time":"0 ... 30 second [unit of time]","Communication":"Modbus-RTU","Terminal Type":"Main Circuit: Bars","Analog Outputs":"4...20 mA","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PSE300","Tightening Torque":"Control Circuit 0.5 N·m","Fault Signal Relay":"Yes","Overload Protection":"Built-in electronic overload protection","Protection Function":"Electronic overload protection, EOL; Locked rotor protection; Current underload protection","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"Yes","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00","Overload Signal Relay":"Yes","Current Limit Function":"1.5 ... 7xIe","Ambient Air Temperature":"Operation -25 ... +60 °C","Rated Operational Voltage":"208 ... 600 V AC","Service Factor Percentage":"100 %","Object Classification Code":"Q","Initial Voltage During Start":"30 ... 70 %","Popular Downloads/EPLAN Data":"9AAC170226_EPLAN","Signal Indication Fault (LED)":"Red","Integrated Electronic Overload":"Yes","Step Down Voltage Special Ramp":"No %","Connecting Capacity Main Circuit":"Hole Diameter 8.5 mm","Material Compliance/WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 250 V AC","Signal Indication Running R (LED)":"Green","Connecting Capacity Supply Circuit":"Rigid 1 x 2.5","IDEA Granular Category Code (IGCC)":"4740 >> Soft starter","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"24 V DC","Signal Indication Protection (LED)":"Yellow","Switch for Inside Delta Connection":"No","Connecting Capacity Control Circuit":"Rigid 1 x 2.5 mm²","Material Compliance/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Signal Indication Ramping Up/Down (LED)":"Green","Popular Downloads/CAD Dimensional Drawing":"2CDC001079B0201","Technical UL/CSA/Horsepower Rating UL/CSA":"(200 ... 208 V AC) Three Phase 100 Hp","Technical UL/CSA/Tightening Torque UL/CSA":"Control Circuit 4.4 in·lb","Popular Downloads/Instructions and Manuals":"1SFC132427M0201","Signal Indication Completed Start Ramp (LED)":"Green","Starting Capacity at Maximum Rated Current Ie":"4xIe for 10s","Rated Operational Power - In-Line Connection (Pe)":"(230 V) 90 kW","Technical UL/CSA/Maximum Operating Voltage UL/CSA":"Main Circuit 600 V","Popular Downloads/Data Sheet, Technical Information":"1SFC132012C0201","Popular Downloads/Instructions and Manuals (Part 2)":"1SFC132057M0201","Popular Downloads/Instructions and Manuals (Part 3)":"1SFC132060M0201","Rated Operational Current - In-Line Connection (Ie)":"300 A","Material Compliance/Toxic Substances Control Act - TSCA":"2CMT2023-006524","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa897114r7001","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA897114R7001/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 1SFA897114R7001?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 1SFA897114R7001's listed function?","answer":"Soft start with torque control — reduces inrush current and mechanical shock during motor start, with adjustable ramp and current limit."},{"question":"What compliance documentation does this brand provide for 1SFA897114R7001?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. WEEE category 5 (small equipment). EPLAN data and CAD dimensional drawing are available."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA897114R7001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA897114R7001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}