{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA898120R7000","brand":"ABB","brandSlug":"abb","productSlug":"1SFA898120R7000","canonicalUrl":"https://aoctrl.com/abb/1SFA898120R7000","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA898120R7000","rawCanonicalId":null},"summary":{"shortDescription":"ABB PSTX1050 soft starter, 1SFA898120R7000, 208-600 V AC, 400 HP at 200-208 V, built-in electronic overload, multi-protocol communication.","salesMarkdown":"The ABB 1SFA898120R7000 is a PSTX1050 soft starter with auto phase sequence detection, designed to ramp three-phase induction motors up and down smoothly, reducing mechanical shock and inrush current. Rated for 208 to 600 V AC at 50/60 Hz, it carries a UL/CSA horsepower rating of 400 Hp at 200-208 V AC three-phase. Built-in electronic overload protection eliminates the need for a separate overload relay, saving panel space and wiring. ## Ramp and protection depth Ramp time is adjustable from 1 to 120 seconds, with initial voltage during start configurable from 10 to 99%. Protection functions include locked rotor, earth fault, phase reversal, under/over voltage, current imbalance, and PT-100 connection for motor thermal monitoring. Warning outputs cover current imbalance, underload, electronic overload time-to-trip, faulty fan, locked rotor, and THD(U) among others. Supports Modbus-RTU, Modbus-TCP, Ethernet/IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP, and BACnet-MSTP — covers nearly every industrial network in a single unit. Analog outputs provide 0-10 V, 0-20 mA, or 4-20 mA signals for external monitoring or trending. Dedicated run, fault, bypass, and overload signal relays are built in, plus a 24 V DC control circuit and a separate 100-250 V AC control supply for the logic. RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863, classified as Business To Business WEEE Category 4 (Large Equipment).","metaTitle":"ABB 1SFA898120R7000 PSTX1050 Soft Starter, 400 HP, 208-600 V","metaDescription":"ABB PSTX1050 soft starter 1SFA898120R7000. 400 HP at 200-208 V, 208-600 V AC, built-in overload, Modbus/Ethernet/IP. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Function":"Auto phase sequence detection","Ramp Time":"1 ... 120 second [unit of time]","Communication":"Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP","Terminal Type":"Main Circuit: Bars","Analog Outputs":"0...10 V, 0...20 mA, 4...20 mA","Warning Details":"Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PSTX1050","Tightening Torque":"Main Circuit 45 N·m","Fault Signal Relay":"Yes","Overload Protection":"Built-in electronic overload protection","Protection Function":"Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"Yes","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00","Overload Signal Relay":"Yes","Current Limit Function":"1.5 ... 7.5 xle","Ambient Air Temperature":"Operation -25 ... +60 °C","Rated Operational Voltage":"208 ... 600 V AC","Service Factor Percentage":"100 %","Object Classification Code":"Q","Initial Voltage During Start":"10 ... 99 %","Popular Downloads/EPLAN Data":"9AAC185675_EPLAN","Signal Indication Fault (LED)":"Red","Integrated Electronic Overload":"Yes","Step Down Voltage Special Ramp":"100 ... 10 %","Material Compliance/WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 250 V AC","Signal Indication Running R (LED)":"Green","Connecting Capacity Supply Circuit":"Rigid 1 x 2.5","IDEA Granular Category Code (IGCC)":"4740 >> Soft starter","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"24 V DC","Signal Indication Protection (LED)":"Yellow","Switch for Inside Delta Connection":"Yes","Connecting Capacity Control Circuit":"Rigid 1 x 2.5 mm²","Material Compliance/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Popular Downloads/CAD Dimensional Drawing":"2CDC001079B0201","Technical UL/CSA/Horsepower Rating UL/CSA":"(200 ... 208 V AC) Three Phase 400 Hp","Technical UL/CSA/Tightening Torque UL/CSA":"Main Circuit 398.3","Popular Downloads/Instructions and Manuals":"1SFC132428M0201","Starting Capacity at Maximum Rated Current Ie":"4xIe for 10s","Rated Operational Power - In-Line Connection (Pe)":"(230 V) 315 kW","Rated Operational Power - Inside Delta Connection":"at 230 V 500 kW","Technical UL/CSA/Maximum Operating Voltage UL/CSA":"Main Circuit 600 V","Popular Downloads/Data Sheet, Technical Information":"1SFC132012C0201","Popular Downloads/Instructions and Manuals (Part 2)":"1SFC132081M0201","Popular Downloads/Instructions and Manuals (Part 3)":"1SFC132060M0201","Rated Operational Current - In-Line Connection (Ie)":"1050 A","Rated Operational Current - Inside Delta Connection":"1810 A","Material Compliance/Toxic Substances Control Act - TSCA":"2CMT2023-006524","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa898120r7000","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA898120R7000/alternatives.json"},"ai":{"faq":[{"question":"What is the function of 1SFA898120R7000?","answer":"Its primary function is auto phase sequence detection, ensuring the motor phase rotation matches the supply before the soft starter engages."},{"question":"What is the ramp time range for this soft starter?","answer":"Ramp time is adjustable from 1 to 120 seconds, with initial voltage configurable from 10 to 99%."},{"question":"What compliance documentation does ABB provide for 1SFA898120R7000?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863, WEEE Category 4 B2B. UL/CSA horsepower rating is documented at 400 Hp at 200-208 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA898120R7000","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA898120R7000 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}