{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"1SFA898210R7000","brand":"ABB","brandSlug":"abb","productSlug":"1SFA898210R7000","canonicalUrl":"https://aoctrl.com/abb/1SFA898210R7000","factsUrl":"https://aoctrl.com/api/mcp/products/1SFA898210R7000","rawCanonicalId":null},"summary":{"shortDescription":"ABB PSTX142 soft starter, order code 1SFA898210R7000, 208…690 V AC, auto phase sequence detection, ramp time 1…120 s, Modbus-RTU/TCP, Ethernet/IP, EtherCAT, Profinet.","salesMarkdown":"The ABB PSTX142 (1SFA898210R7000) is a soft starter with built-in auto phase sequence detection — it verifies the incoming phase rotation before the motor starts, so you don't risk a reverse-spinning conveyor or pump on commissioning. Ramp time is adjustable from 1 to 120 seconds, which lets you tune the acceleration for the load — a loaded crusher needs a longer ramp than a light fan. The control circuit runs on 24 V DC; the main control supply accepts 100…250 V AC, so the logic stays isolated from the power stage. ## Communications and integration This unit speaks Modbus-RTU, Modbus-TCP, Ethernet/IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP, and BACnet-MSTP — essentially every fieldbus you'll find in a modern panel. That means the PSTX142 drops into a greenfield EtherCAT line or a legacy Profibus installation without a gateway. The main circuit terminals are bars; torque them to 14 N·m. Analog outputs are configurable as 0…10 V, 0…20 mA, or 4…20 mA, so you can feed a speed reference or current signal to a PLC analog card directly. ## Protection and diagnostics Electronic overload protection is built in — no separate overload relay needed. The protection suite covers current imbalance, underload, earth fault, locked rotor, over/under voltage, phase reversal, PTC/PT-100 motor thermal inputs, and a user-defined protection set. That's a lot of ground fault and thermal coverage without external modules. Warning outputs flag 15 conditions including faulty fan, EOL, thyristor overload, and THD(U). Separate signal relays for run, fault, bypass, and overload give discrete status back to the controller. LED indicators on the front (green run, red fault, yellow protection) let a technician read the state at a glance.","metaTitle":"1SFA898210R7000 ABB PSTX142 Soft Starter, 208-690V AC, Auto","metaDescription":"ABB PSTX142 soft starter 1SFA898210R7000. 208-690V AC, auto phase sequence detection, ramp time 1-120s, Modbus/Ethernet/IP. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Function":"Auto phase sequence detection","Ramp Time":"1 ... 120 second [unit of time]","Communication":"Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP","Terminal Type":"Main Circuit: Bars","Analog Outputs":"0...10 V, 0...20 mA, 4...20 mA","Warning Details":"Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning","lifecycle_stage":"current","Run Signal Relay":"Yes","Product Main Type":"PSTX142","Tightening Torque":"Main Circuit 14 N·m","Fault Signal Relay":"Yes","Overload Protection":"Built-in electronic overload protection","Protection Function":"Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection","Rated Frequency (f)":"50/60 Hz","By-pass Signal Relay":"Yes","Degree of Protection":"acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00","Overload Signal Relay":"Yes","Current Limit Function":"1.5 ... 7.5 xle","Ambient Air Temperature":"Operation -25 ... +60 °C","Material Compliance/SCIP":"7ac58c93-1935-4f9a-a1cf-b53a16b37b9e Sweden","Rated Operational Voltage":"208 ... 690 V AC","Service Factor Percentage":"100 %","Object Classification Code":"Q","Initial Voltage During Start":"10 ... 99 %","Popular Downloads/EPLAN Data":"9AAC181166_EPLAN","Signal Indication Fault (LED)":"Red","Integrated Electronic Overload":"Yes","Step Down Voltage Special Ramp":"100 ... 10 %","Connecting Capacity Main Circuit":"Hole Diameter 8.5 mm","Material Compliance/WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Rated Control Supply Voltage (Us)":"100 ... 250 V AC","Signal Indication Running R (LED)":"Green","Connecting Capacity Supply Circuit":"Rigid 1 x 2.5","IDEA Granular Category Code (IGCC)":"4740 >> Soft starter","Material Compliance/WEEE B2C / B2B":"Business To Business","Rated Control Circuit Voltage (Uc)":"24 V DC","Signal Indication Protection (LED)":"Yellow","Switch for Inside Delta Connection":"Yes","Connecting Capacity Control Circuit":"Rigid 1 x 2.5 mm²","Material Compliance/Simplified SCIP":"2c12831e-d227-4343-89cd-8ad9d0598b61 Croatia","Material Compliance/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Popular Downloads/CAD Dimensional Drawing":"2CDC001079B0201","Technical UL/CSA/Horsepower Rating UL/CSA":"(200 ... 208 V AC) Three Phase 40 Hp","Technical UL/CSA/Tightening Torque UL/CSA":"Main Circuit 123.9","Popular Downloads/Instructions and Manuals":"1SFC132428M0201","Starting Capacity at Maximum Rated Current Ie":"4xIe for 10s","Rated Operational Power - In-Line Connection (Pe)":"(230 V) 37 kW","Rated Operational Power - Inside Delta Connection":"at 230 V 75 kW","Technical UL/CSA/Maximum Operating Voltage UL/CSA":"Main Circuit 690 V","Popular Downloads/Data Sheet, Technical Information":"1SFC132012C0201","Popular Downloads/Instructions and Manuals (Part 2)":"1SFC132081M0201","Popular Downloads/Instructions and Manuals (Part 3)":"1SFC132060M0201","Rated Operational Current - In-Line Connection (Ie)":"142 A","Rated Operational Current - Inside Delta Connection":"245 A","Material Compliance/Toxic Substances Control Act - TSCA":"2CMT2023-006524","Material Compliance/Conflict Minerals Reporting Template (CMRT)":"9AKK108467A5658"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/1sfa898210r7000","alternativesUrl":"https://aoctrl.com/api/mcp/products/1SFA898210R7000/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 1SFA898210R7000 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What does auto phase sequence detection mean on this soft starter?","answer":"It checks the incoming phase rotation (-L2-L3 order) before the motor starts and will not energize if the sequence is reversed, preventing a motor from running backward. This is a built-in function, not an add-on module."},{"question":"What is the ramp time range on the PSTX142?","answer":"The ramp time is adjustable from 1 to 120 seconds, letting you match the acceleration profile to the load inertia — short for low-inertia fans, long for high-inertia conveyors or crushers."},{"question":"What compliance documentation is available for 1SFA898210R7000?","answer":"WEEE category 5 (small equipment, B2B), SCIP substance declarations for Sweden and Croatia, and material compliance data are on file. The part is compliant with current EU substance regulations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/1SFA898210R7000","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/1SFA898210R7000 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}