{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"2CCF004155R0001","brand":"ABB","brandSlug":"abb","productSlug":"2CCF004155R0001","canonicalUrl":"https://aoctrl.com/abb/2CCF004155R0001","factsUrl":"https://aoctrl.com/api/mcp/products/2CCF004155R0001","rawCanonicalId":null},"summary":{"shortDescription":"ABB, motor protection circuit breaker, 2CCF004155R0001, 3-pole, 1.6–2.5 A overload range, Class 10, 400 V, IP20.","salesMarkdown":"The ABB 2CCF004155R0001 is a 3-pole motor protection circuit breaker sized for the 1.6–2.5 A overload range. Class 10 tripping means it clears a stalled rotor fast enough to protect standard IEC induction motors before the winding insulation takes heat damage — that's the trip class you want for pumps, fans, and compressors on a general-purpose line. Rated operating voltage maxes out at 400 V, which covers most 230/400 V three-phase panels. IP20 finger-safe housing means it belongs inside a panel, not out on the wet floor. The 54 mm depth and 94.5 mm width fit a standard DIN-rail footprint; you can stack it next to a contactor without eating into the next row. Terminals accept 0.75–6 mm² flexible copper — fine for the motor leads on a sub-2.5 A circuit. Rated for 100,000 mechanical cycles — that's a long service life for a manual motor starter in a panel that sees regular switching.","metaTitle":"ABB 2CCF004155R0001 Motor Protection Circuit Breaker, 2.5A,","metaDescription":"ABB motor protection circuit breaker 2CCF004155R0001, 3-pole, 1.6-2.5 A overload range, Class 10 trip, 400 V, IP20. Current production; available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"54 mm","Poles":"3","Width":"94.5 mm","title":"2CCF004155R0001","Height":"90 mm","description":"Motor Protection Circuit Breaker, 2.5A, 400V","Tripping class":"Class 10","lifecycle_stage":"current","Protection rating":"IP 20","Overload release max.":"2.5 A","Overload release min.":"1.6 A","Rated operating current":"2.5","Service life, mechanical":"100 000 cycles","Operating temperature max.":"50 °C","Operating temperature min.":"-25 °C","Cross-section, flexible max.":"6 mm²","Cross-section, flexible min.":"0.75 mm²","Rated operating voltage max.":"400 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c32d3adbbf6a840db92bebf90dd20508.pdf","sourceUrl":null},"ai":{"faq":[{"question":"Where can I buy the 2CCF004155R0001 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the overload range on this motor circuit breaker?","answer":"The overload release range is 1.6 A minimum to 2.5 A maximum. That means the thermal adjustment dial covers motors drawing between those full-load amps, with Class 10 trip characteristics."},{"question":"What is the closest alternative to the 2CCF004155R0001?","answer":"Within the same ABB manual motor starter family, the closest peer would share the same 3-pole frame and Class 10 trip curve but with a different overload range. The deciding factor is your motor's full-load current — this unit covers 1.6–2.5 A, so a peer with an adjacent range (e.g., 2.5–4 A) would be the next step up. No pin-compatible drop-in exists outside that range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/2CCF004155R0001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/2CCF004155R0001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}