{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"2CCS471001R0134","brand":"ABB","brandSlug":"abb","productSlug":"2CCS471001R0134","canonicalUrl":"https://aoctrl.com/abb/2CCS471001R0134","factsUrl":"https://aoctrl.com/api/mcp/products/2CCS471001R0134","rawCanonicalId":null},"summary":{"shortDescription":"ABB miniature circuit breaker, 1-pole, C-curve, 13 A, 440 V, IP20, DIN rail mount.","salesMarkdown":"The 2CCS471001R0134 is a 1-pole miniature circuit breaker with a C-curve trip characteristic, rated 13 A at 440 V insulation voltage. The 10 kA Icn (service breaking capacity) and 25 kA Icu (ultimate breaking capacity) give selectivity headroom for a 400 V distribution board; the Icu figure tells you the breaker can safely interrupt a fault up to 25 kA once and still be functional afterward, while Icn is the guaranteed performance for repeated operation. ## Integration into the enclosure The 69 mm width (roughly 4 module spaces) and 94.5 mm depth fit a standard distribution board or sub-panel. Screw terminals accept solid or stranded copper; strip length per ABB termination practice (typically 10–12 mm) avoids creepage issues at 440 V.","metaTitle":"ABB 2CCS471001R0134 MCB, C-curve 13A, 1-pole, 10kA","metaDescription":"ABB miniature circuit breaker, 1-pole, C-curve, 13 A rated, 440 V insulation, 10 kA Icn / 25 kA Icu. DIN rail mount, IP20. Current production — sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["MCCB up to 100A"],"specifications":{"Depth":"94.5 mm","Poles":"1","Width":"69 mm","title":"2CCS471001R0134","Height":"89 mm","IP Rating":"IP20","description":"Miniature Circuit Breaker, C, 13A, 440V, IP20","Mounting Type":"DIN Rail Mount","Rated Current":"13 A","lifecycle_stage":"current","Overvoltage Category":"III","Terminal Contact Type":"Screw","Rated Insulation Voltage":"440 V","Tripping Characteristics":"C","Rated Short-Circuit Breaking Capacity Icn":"10 kA","Rated Short-Circuit Breaking Capacity Icu":"25 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$25.40","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a8e59a95bf4da3aa0c9edbbcc41eef85.pdf","sourceUrl":null},"ai":{"faq":[{"question":"Where can I buy 2CCS471001R0134 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"What are the key ratings for 2CCS471001R0134?","answer":"1-pole, C-curve, 13 A rated current, 440 V insulation voltage, 10 kA Icn / 25 kA Icu breaking capacity, IP20, DIN rail mount."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/2CCS471001R0134","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/2CCS471001R0134 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}