{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"2CCS471001R0164","brand":"ABB","brandSlug":"abb","productSlug":"2CCS471001R0164","canonicalUrl":"https://aoctrl.com/abb/2CCS471001R0164","factsUrl":"https://aoctrl.com/api/mcp/products/2CCS471001R0164","rawCanonicalId":null},"summary":{"shortDescription":"ABB, miniature circuit breaker, 2CCS471001R0164, 1-pole, C-curve, 16 A, 10 kA Icn, 25 kA Icu, 440 V, IP20, DIN rail mount.","salesMarkdown":"The 10 kA Icn (rated short-circuit breaking capacity per IEC 60898) is the service breaking capacity for standard distribution panels; the 25 kA Icu (ultimate breaking capacity per IEC 60947-2) tells you the breaker can safely interrupt a fault up to 25 kA once, which matters when it's installed in a high-fault location like an industrial sub-distribution board. The 440 V rated insulation voltage covers 400 V three-phase line-to-line systems common in European and Asian panels. ## Panel integration and deployment IP20 finger-safe terminals with screw clamps accept solid or stranded copper up to 25 mm². Listed as current production stage.","metaTitle":"ABB 2CCS471001R0164 MCB, C-16A, 1P, 10kA Icn","metaDescription":"ABB miniature circuit breaker, 1-pole, 16 A, C-curve, 10 kA Icn / 25 kA Icu, 440 V, IP20, DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"94.5 mm","Poles":"1","Width":"69 mm","Height":"89 mm","IP Rating":"IP20","Mounting Type":"DIN Rail Mount","Rated Current":"16 A","lifecycle_stage":"current","Overvoltage Category":"III","Terminal Contact Type":"Screw","Rated Insulation Voltage":"440 V","Tripping Characteristics":"C","Rated Short-Circuit Breaking Capacity Icn":"10 kA","Rated Short-Circuit Breaking Capacity Icu":"25 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$53.40 – $56.20","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/13924bdc1243c7b2f3763af1a6981b52.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/2CCS471001R0164/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCB?","answer":"Rated short-circuit breaking capacity Icn is 10 kA per IEC 60898; ultimate breaking capacity Icu is 25 kA per IEC 60947-2. The higher Icu figure applies when the breaker is used as a selective device in an industrial distribution scheme."},{"question":"Where can I buy 2CCS471001R0164?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What does the C-curve mean for my application?","answer":"The C tripping characteristic (5–10× In) is suited for circuits with moderate inrush currents — typical for small motors, transformers, discharge lighting, and general-purpose inductive loads. For purely resistive loads or long cable runs with high starting currents, a B-curve or D-curve may be more appropriate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/2CCS471001R0164","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/2CCS471001R0164 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}