{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"2CCS862001R0104","brand":"ABB","brandSlug":"abb","productSlug":"2CCS862001R0104","canonicalUrl":"https://aoctrl.com/abb/2CCS862001R0104","factsUrl":"https://aoctrl.com/api/mcp/products/2CCS862001R0104","rawCanonicalId":null},"summary":{"shortDescription":"ABB High Performance Miniature Circuit Breaker, C-curve, 10 A, 2-pole, 690 V rated insulation voltage, 25 kA Icn / 50 kA Icu breaking capacity, IP20, DIN rail mount.","salesMarkdown":"The 25 kA Icn (rated short-circuit breaking capacity per IEC 60898) is the service breaking capacity for general distribution; the 50 kA Icu (ultimate breaking capacity per IEC 60947-2) is the maximum fault it can clear once and still be functional afterward. Rated insulation voltage of 690 V and overvoltage category IV mean this breaker is rated for the line side of the installation — at the service entrance or main distribution board — not just downstream subpanels. Overvoltage category IV is the highest within the IEC 60947-2 framework, covering equipment connected to the utility supply point. That makes this part suitable for main incoming feeders in 400/690 V industrial networks. Dimensions are 54 mm wide (2-pole width, 2 x 18 mm per pole), 95 mm tall, 82.5 mm deep. The 82.5 mm depth includes the breaker body and the screw terminals — account for that when laying out the enclosure depth, especially in shallow wall-mount boxes. IP20 finger-safe terminals mean the front face is touch-safe once installed, but the breaker is not sealed against dust or moisture; it belongs inside a panel with a door.","metaTitle":"2CCS862001R0104 MCB, C-curve 10A, 2-pole, 25kA Icn","metaDescription":"High Performance MCB, C-curve, 10A, 2-pole, 690V insulation, 25kA Icn / 50kA Icu breaking capacity, IP20, DIN rail. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"82.5 mm","Poles":"2","Width":"54 mm","title":"2CCS862001R0104","Height":"95 mm","IP Rating":"IP20","description":"High Performance Miniature Circuit Breaker, C, 10A, 690V, IP20","Mounting Type":"DIN Rail Mount","Rated Current":"10 A","lifecycle_stage":"current","Overvoltage Category":"IV","Terminal Contact Type":"Screw","Rated Insulation Voltage":"690 V","Tripping Characteristics":"C","Rated Short-Circuit Breaking Capacity Icn":"25 kA","Rated Short-Circuit Breaking Capacity Icu":"50 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$214.56 – $220.11","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5b841109e9a6f04760d8437271d13097.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"Rated short-circuit breaking capacity Icn is 25 kA per IEC 60898; ultimate breaking capacity Icu is 50 kA per IEC 60947-2. The 25 kA Icn is the service rating for general distribution; the 50 kA Icu is the maximum fault it can clear once."},{"question":"What does the C-curve mean for this 10 A breaker?","answer":"The C-curve trips at 5 to 10 times rated current (50 to 100 A magnetic trip). It is intended for circuits with moderate inrush — small motors, transformers, capacitor banks — where a B-curve would trip on startup surge."},{"question":"What is the physical size of this breaker?","answer":"Width 54 mm (2-pole, 18 mm per pole), height 95 mm, depth 82.5 mm. Mounts on 35 mm DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/2CCS862001R0104","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/2CCS862001R0104 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}