{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"2CDS271103R0064","brand":"ABB","brandSlug":"abb","productSlug":"2CDS271103R0064","canonicalUrl":"https://aoctrl.com/abb/2CDS271103R0064","factsUrl":"https://aoctrl.com/api/mcp/products/2CDS271103R0064","rawCanonicalId":null},"summary":{"shortDescription":"ABB S200 series miniature circuit breaker, 2CDS271103R0064, C-curve, 6 A, 2-pole, 440 V rated insulation voltage, 10 kA Icn / 25 kA Icu, DIN-rail mount, IP20/IP40.","salesMarkdown":"The 10 kA Icn (rated short-circuit breaking capacity per EN 60898) and 25 kA Icu (ultimate breaking capacity per IEC 60947-2) tell you this breaker can safely interrupt fault currents up to those levels at 440 V, which covers most commercial and light industrial panel applications. The 440 V rated insulation voltage (Ui) confirms it's rated for 400 V three-phase systems with margin. ## Panel integration and deployment Dimensions: 88 mm high, 35 mm wide per pole (so 70 mm wide for this 2-pole unit), 69 mm deep. The bi-directional cylinder-lift terminals accept up to 2.8 Nm tightening torque.","metaTitle":"ABB 2CDS271103R0064 MCB, C-Curve 6A 2-Pole, 10 kA","metaDescription":"ABB S200 series miniature circuit breaker, 6 A rated, C tripping characteristic, 2-pole, 440 V insulation voltage, 10 kA Icn / 25 kA Icu breaking capacity. DIN-rail mount, IP20/IP4","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"69 mm","Poles":"2","Width":"35 mm","Height":"88 mm","IP Rating":"IP20;IP40","Mounting Type":"DIN Rail Mount","Rated Current":"6 A","lifecycle_stage":"current","Overvoltage Category":"III","Terminal Contact Type":"Bi-Directional Cylinder Lift","Rated Insulation Voltage":"440 V","Tripping Characteristics":"C","Tightening Torque - Screw-Type Max.":"2.8 Nm","Rated Short-Circuit Breaking Capacity Icn":"10 kA","Rated Short-Circuit Breaking Capacity Icu":"25 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$94.50 – $109.40","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a963bd5fceef66361105c94b2d8f275.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/2CDS271103R0064/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 2CDS271103R0064?","answer":"Rated short-circuit breaking capacity Icn is 10 kA per EN 60898; ultimate breaking capacity Icu is 25 kA per IEC 60947-2 at 440 V."},{"question":"Where can I buy 2CDS271103R0064?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What does the C-curve mean on this breaker?","answer":"The C tripping characteristic means the magnetic trip operates at 5–10 times rated current (30–60 A for this 6 A unit), making it suitable for circuits with moderate inrush like small motors or capacitor banks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/2CDS271103R0064","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/2CDS271103R0064 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}