{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"2CDS272001R0064","brand":"ABB","brandSlug":"abb","productSlug":"2CDS272001R0064","canonicalUrl":"https://aoctrl.com/abb/2CDS272001R0064","factsUrl":"https://aoctrl.com/api/mcp/products/2CDS272001R0064","rawCanonicalId":null},"summary":{"shortDescription":"ABB, System pro M compact S200 series, miniature circuit breaker, C-curve, 6 A, 2-pole, 440 V, 10 kA Icn, DIN rail mount, IP20/IP40.","salesMarkdown":"The ABB 2CDS272001R0064 is a C-curve miniature circuit breaker rated 6 A, 2-pole, with a rated insulation voltage of 440 V. The 10 kA Icn (rated short-circuit breaking capacity per IEC 60898) tells you it can safely clear a fault up to that level on the downstream side; the 25 kA Icu (per IEC 60947-2) is the ultimate capacity it can handle once before needing replacement — that extra headroom matters for selectivity coordination in a panel where upstream devices need to see the fault first. Snaps onto a standard DIN rail — 35 mm wide, 88 mm tall, 69 mm deep. The IP20 rating on the front means finger-safe from the face; IP40 on the enclosure body keeps out tools and wires over 1 mm. Overvoltage category III suits fixed-installation distribution panels where transients from the utility side are expected. Terminal torque spec of 2.8 Nm for the screw-type bi-directional cylinder lift terminals — standard for 2.5 mm² to 6 mm² conductors in a panel-building workflow.","metaTitle":"ABB 2CDS272001R0064 MCB, C-Curve 6A, 2-Pole, 10kA","metaDescription":"ABB 2CDS272001R0064 miniature circuit breaker, C-curve, 6 A, 2-pole, 440 V, 10 kA Icn. DIN rail mount, IP20/IP40. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"69 mm","Poles":"2","Width":"35 mm","title":"2CDS272001R0064","Height":"88 mm","IP Rating":"IP20;IP40","description":"Miniature Circuit Breaker, C, 6A, 440V, IP20 / IP40","Mounting Type":"DIN Rail Mount","Rated Current":"6 A","lifecycle_stage":"current","Overvoltage Category":"III","Terminal Contact Type":"Bi-Directional Cylinder Lift","Rated Insulation Voltage":"440 V","Tripping Characteristics":"C","Tightening Torque - Screw-Type Max.":"2.8 Nm","Rated Short-Circuit Breaking Capacity Icn":"10 kA","Rated Short-Circuit Breaking Capacity Icu":"25 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$131.31 – $151.96","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a963bd5fceef66361105c94b2d8f275.pdf","sourceUrl":null},"ai":{"faq":[{"question":"Where can I buy 2CDS272001R0064 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the breaking capacity of this MCB?","answer":"Rated short-circuit breaking capacity Icn is 10 kA per IEC 60898; ultimate breaking capacity Icu is 25 kA per IEC 60947-2."},{"question":"What does the C-curve mean for this 6 A breaker?","answer":"The C-curve trips at 5 to 10 times rated current (30–60 A magnetic trip), suited for circuits with moderate inrush like lighting or small motor loads where a B-curve would nuisance-trip but a D-curve is unnecessary."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/2CDS272001R0064","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/2CDS272001R0064 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}