{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00036866-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00036866-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00036866-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00036866-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-04 LV AC general purpose drive module, 3ABD00036866-D, 500 kW / 880 A normal use, IP00, Frame R11, IE2.","salesMarkdown":"## Normal-use vs heavy-duty — which rating governs your load The 3ABD00036866-D: The normal-use rating (500 kW, 880 A) covers constant-torque applications like pumps and fans. The heavy-duty rating (400 kW, 725 A) applies to higher-torque profiles — conveyors, crushers, extruders. If your load profile sits between these, the light-overload rating (500 kW, 865 A) is also listed. Match the duty cycle to the column that fits, not the headline number. ## Cabinet-built — plan for integration Mounting type is cabinet-built with no unit enclosure — IP00 and NEMA Open Type. That means it's designed to be built into a panel or cabinet, not surface-mounted on a wall. Frame R11 gives you the physical footprint for panel layout; plan for proper cooling and clearance around the open chassis.","metaTitle":"ABB 3ABD00036866-D ACS580-04 Drive Module, 500 kW, 880 A","metaDescription":"ABB 3ABD00036866-D ACS580-04 LV AC drive module, 500 kW normal use, 880 A output, IP00, IE2. Active production. Frame R11. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP00","Output Power, Normal Use (Pn)":"500 kW","Output Current, Normal Use (In)":"880 A","Output Power, Heavy-Duty Use (PhD)":"400 kW","Output Current, Heavy-Duty Use (IhD)":"725 A","Output Power, Light-Overload Use (PlD)":"500 kW","Output Current, Light-Overload Use (IlD)":"865 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00036866-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00036866-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive module?","answer":"Normal use: 500 kW at 880 A. Heavy-duty use: 400 kW at 725 A. Light-overload use: 500 kW at 865 A."},{"question":"What is the frame size and enclosure type?","answer":"Frame size R11, IP00 open-type enclosure (NEMA Open Type). It is a cabinet-built unit, not a standalone drive."},{"question":"What input voltage and frequency does it accept?","answer":"Three-phase 380–480 V AC, 47.5–63 Hz."},{"question":"What efficiency level does this drive meet?","answer":"IE2 efficiency level."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00036866-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00036866-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}