{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00037856-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00037856-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00037856-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00037856-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 series, LV AC industrial wall-mounted single drive, 3ABD00037856-D, 75 kW normal use, 124 A output current, 380-500 V input, IP21, NEMA Type 1, IE2 efficiency.","salesMarkdown":"## Frame size and mounting The 3ABD00037856-D: Frame size R6. Wall-mounted — no floor stand needed. The IP21 / NEMA 1 enclosure keeps dust and drips out but isn't rated for washdown. Plan gland plate access accordingly; the R6 frame has generous cable entry but still needs clearance for bending radius on 124 A power cables. ## Duty ratings — normal, heavy, light overload Three duty ratings cover the application range. Heavy-duty (PhD 55 kW, IhD 96 A) for high-starting-torque or cyclic loads — crushers, extruders. Light-overload (PlD 75 kW, IlD 118 A) for variable-torque fans and centrifugal pumps where peak demand is brief. Pick the rating that matches your load profile; the drive's thermal model uses the same hardware.","metaTitle":"ABB 3ABD00037856-D ACS880-01 Drive, 75 kW, 124 A","metaDescription":"ABB 3ABD00037856-D ACS880-01 wall-mounted drive, 75 kW normal use, 124 A output, 380-500 V input, IP21, NEMA 1, IE2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"124 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"96 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"118 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00037856-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00037856-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00037856-D?","answer":"Frame size R6. It is a wall-mounted drive, not floor-standing."},{"question":"What is the input voltage and frequency range?","answer":"Input voltage is 380-500 V three-phase, frequency 47.5-63 Hz."},{"question":"What are the output power and current ratings?","answer":"Normal use: 75 kW, 124 A. Heavy-duty: 55 kW, 96 A. Light-overload: 75 kW, 118 A."},{"question":"What enclosure and protection rating does it have?","answer":"NEMA Type 1 enclosure with IP21 degree of protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00037856-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00037856-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}