{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00037857-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00037857-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00037857-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00037857-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 wall-mounted single drive, 90 kW normal duty, 156 A output, 380-500 V 3-phase, IP21, NEMA 1.","salesMarkdown":"The 3ABD00037857-D: Normal-use output (156 A) covers constant-torque applications like pumps and fans at 90 kW. Heavy-duty (124 A, 75 kW) is the figure for high-starting-torque or cyclic loads — conveyors, crushers, extruders. Light-overload rating (148 A) sits between them. Match your motor's full-load amps to the appropriate column; the drive's thermal model handles the rest. ## Installation notes Wall-mount only — no floor-standing kit included. IP21 and NEMA 1 suit clean indoor environments. Frame R7 determines the mounting footprint and cable entry layout; verify panel depth against the drive's heat sink projection. Efficiency class IE2.","metaTitle":"ABB 3ABD00037857-D ACS880-01 Drive, 90 kW, 156 A","metaDescription":"ABB ACS880-01 wall-mounted drive, 90 kW normal duty, 156 A output, 380-500 V 3-phase, IP21, NEMA 1, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R7","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"90 kW","Output Current, Normal Use (In)":"156 A","Output Power, Heavy-Duty Use (PhD)":"75 kW","Output Current, Heavy-Duty Use (IhD)":"124 A","Output Power, Light-Overload Use (PlD)":"90 kW","Output Current, Light-Overload Use (IlD)":"148 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00037857-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00037857-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R7."},{"question":"What are the normal-duty and heavy-duty ratings?","answer":"Normal duty: 90 kW, 156 A. Heavy duty: 75 kW, 124 A. Light overload: 90 kW, 148 A."},{"question":"What input voltage and frequency does it accept?","answer":"380-500 V 3-phase, 47.5-63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00037857-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00037857-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}