{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00038132-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00038132-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00038132-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00038132-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 wall-mounted industrial drive, 75 kW normal-use output, 124 A, 380-500 V, 3-phase, IP21, NEMA 1, Frame R6, IE2.","salesMarkdown":"## Sizing and duty class The 3ABD00038132-D: Normal-use (Pn 75 kW, In 124 A) covers constant-torque loads like conveyors and pumps. Heavy-duty (PhD 55 kW, IhD 96 A) handles higher peak demands — crushers, extruders, or rapid acceleration profiles. Light-overload rating (PlD 75 kW, IlD 118 A) matches normal-use power but at slightly lower current, useful for variable-torque fans or centrifugal pumps where overload margin is less critical. Wall-mounted, frame R6. IP21 and NEMA Type 1 mean it's suitable for indoor, dry locations — no washdown or dust-tight rating. The enclosure keeps out fingers and falling dirt, but not moisture spray or airborne dust. Plan for a filtered fan intake if the cabinet sees particulates.","metaTitle":"3ABD00038132-D ABB ACS880-01-124A-5+D150+E200 75 kW Drive, 1","metaDescription":"ABB ACS880-01 wall-mounted drive, 75 kW normal-use output, 124 A, 380-500 V, IP21, NEMA 1, IE2. Active production — sourced to order. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"124 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"96 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"118 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00038132-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00038132-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R6."},{"question":"What is the input voltage and frequency range?","answer":"380-500 V three-phase, 47.5-63 Hz."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal-use: 75 kW, 124 A. Heavy-duty: 55 kW, 96 A."},{"question":"What enclosure protection does it have?","answer":"IP21 and NEMA Type 1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00038132-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00038132-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}