{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00038170-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00038170-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00038170-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00038170-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01, LV AC industrial wall-mounted single drive, IEC: Pn 200 kW, 363 A (3ABD00038170-D), frame R9, IP21, 380-415 V 3-phase.","salesMarkdown":"The ABB 3ABD00038170-D is an ACS880-01 wall-mounted single drive rated for 200 kW normal use at 363 A output, with a heavy-duty rating of 160 kW at 293 A. It runs on 380-415 V three-phase input across 47.5 to 63 Hz, and carries an IP21 enclosure with NEMA Type 1. Frame size is R9. The 363 A normal-use current is the number to match against your motor full-load amps plus service factor — that's the continuous rating for typical pump/fan loads. The heavy-duty 293 A figure (160 kW) is the one for constant-torque applications like conveyors or extruders where you need headroom for short-term overloads. Input voltage range of 380-415 V covers standard European and much of Asian low-voltage networks; the 47.5-63 Hz frequency window handles both 50 Hz and 60 Hz grids without derating. The NEMA Type 1 equivalent means no additional weatherproofing needed for indoor installation. Plan for top/bottom cable entry and adequate clearance for the cooling airflow.","metaTitle":"ABB 3ABD00038170-D ACS880-01 Drive, 200 kW, 363 A, IP21","metaDescription":"ABB ACS880-01 wall-mounted drive, 200 kW normal use, 363 A output, 380-415 V input, IP21, frame R9. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R9","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"200 kW","Output Current, Normal Use (In)":"363 A","Output Power, Heavy-Duty Use (PhD)":"160 kW","Output Current, Heavy-Duty Use (IhD)":"293 A","Output Power, Light-Overload Use (PlD)":"200 kW","Output Current, Light-Overload Use (IlD)":"345 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00038170-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00038170-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00038170-D?","answer":"Frame size is R9."},{"question":"What are the normal-use and heavy-duty ratings?","answer":"Normal use: 200 kW, 363 A. Heavy-duty use: 160 kW, 293 A. Light-overload use: 200 kW, 345 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00038170-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00038170-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}