{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00038199-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00038199-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00038199-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00038199-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACS880-01 series, LV AC industrial wall-mounted single drive, 90 kW / 156 A normal use, 380-500 V 3-phase, IP21, IE2, frame size R7.","salesMarkdown":"## Drive selection memo — ACS880-01 at 90 kW The ABB 3ABD00038199-D is a wall-mounted single drive rated for 90 kW normal use (156 A) and 75 kW heavy-duty use (124 A) on a 380-500 V three-phase supply. Frame size R7; IP21; IE2. ## Duty ratings — normal vs heavy Three duty ratings: 90 kW / 156 A normal-use, 90 kW / 148 A light-overload, and 75 kW / 124 A heavy-duty. Heavy-duty governs for constant-torque loads; normal-use for variable-torque loads. Wall-mounted, NEMA Type 1 enclosure. Frame size R7. Frequency range 47.5-63 Hz. WEEE category 4. IE2 efficiency.","metaTitle":"ABB 3ABD00038199-D ACS880-01 Drive, 90 kW, 156 A, IP21","metaDescription":"ABB ACS880-01 wall-mounted drive, 90 kW normal use, 156 A output, 380-500 V 3-phase, IP21, IE2. Active production. Frame size R7. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R7","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"90 kW","Output Current, Normal Use (In)":"156 A","Output Power, Heavy-Duty Use (PhD)":"75 kW","Output Current, Heavy-Duty Use (IhD)":"124 A","Output Power, Light-Overload Use (PlD)":"90 kW","Output Current, Light-Overload Use (IlD)":"148 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00038199-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00038199-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R7. That's the larger wall-mount frame in the ACS880-01 family, so plan for the physical dimensions when designing the panel layout."},{"question":"What are the normal-use and heavy-duty ratings?","answer":"Normal-use output is 90 kW / 156 A; heavy-duty output is 75 kW / 124 A. Light-overload use is rated 90 kW / 148 A."},{"question":"What is the enclosure protection rating?","answer":"IP21 / NEMA Type 1. Suitable for indoor, dry locations; not rated for washdown or outdoor installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00038199-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00038199-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}