{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00038233-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00038233-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00038233-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00038233-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01, wall-mounted single drive, 132 kW normal-use output, 240 A, frame size R8, IP21, NEMA 1, IE2.","salesMarkdown":"The ABB 3ABD00038233-D is a wall-mounted single drive rated for 132 kW normal-use output at 240 A, with a heavy-duty rating of 110 kW at 180 A. It runs on 380–500 V three-phase input, 47.5–63 Hz, and carries IE2 efficiency. Enclosure is IP21 / NEMA Type 1, frame size R8. The 240 A normal-use output current (In) is the number to match against your motor full-load amps at rated voltage. If the application cycles hard — conveyors, crushers, pumps with high breakaway torque — the heavy-duty curve (110 kW, 180 A) is the one that holds takt time. The IE2 efficiency class means the drive meets the minimum for most industrial installations, though some sites now spec IE3 or IE4; verify your local code. Wall-mounted, frame size R8. IP21 covers indoor installations where dripping water is absent; NEMA Type 1 is equivalent. The enclosure is sized for a 132 kW drive with 240 A output.","metaTitle":"ABB 3ABD00038233-D ACS880-01 Drive, 132 kW, 240 A, R8","metaDescription":"Active ABB ACS880-01 wall-mounted drive, 132 kW normal-use, 240 A output, IP21, NEMA 1, IE2. Frame size R8. Sourced to order. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R8","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"132 kW","Output Current, Normal Use (In)":"240 A","Output Power, Heavy-Duty Use (PhD)":"110 kW","Output Current, Heavy-Duty Use (IhD)":"180 A","Output Power, Light-Overload Use (PlD)":"132 kW","Output Current, Light-Overload Use (IlD)":"228 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00038233-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00038233-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output: 132 kW at 240 A. Heavy-duty output: 110 kW at 180 A. Input: 380–500 V three-phase, 47.5–63 Hz. Efficiency class IE2. Frame size R8. Enclosure IP21 / NEMA Type 1."},{"question":"How do I source this drive?","answer":"This is an active-production part sourced to order. Submit an RFQ for current lead time and pricing. No stock is held on this listing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00038233-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00038233-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}