{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039326-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039326-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039326-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039326-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 LV AC industrial single drive module, 355 kW / 503 A normal use, 380-500 V 3-phase input, IP20, frame R10.","salesMarkdown":"The ABB 3ABD00039326-D is an LV AC industrial single drive module rated for 355 kW normal use at 503 A, with a heavy-duty output of 250 kW at 361 A and a light-overload output of 355 kW at 483 A. It runs on a 380-500 V 3-phase input at 47.5-63 Hz, in an IP20 open-type enclosure, frame size R10. The key decision point is matching the duty cycle. Normal-use 503 A covers continuous motor loads at 355 kW; heavy-duty 361 A at 250 kW handles high-torque starts or cyclic overloads. Light-overload 483 A sits between them. If your application is a pump or fan, normal-use is the spec to check. For a crusher or conveyor, size against the heavy-duty line. Input voltage range of 380-500 V covers 47.5-63 Hz frequency tolerance for weak grids or genset feeds. IP20 open-type enclosure means it's for indoor cabinet mounting only — no washdown or dust. Frame R10 dictates the physical footprint and bus-bar layout; verify cabinet depth and bus-bar centers against the existing panel.","metaTitle":"ABB 3ABD00039326-D ACS880-04 Drive Module, 355 kW / 503 A","metaDescription":"Active ABB ACS880-04 drive module, 355 kW normal use at 503 A, 380-500 V 3-phase input, IP20, frame R10. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R10","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"355 kW","Output Current, Normal Use (In)":"503 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"361 A","Output Power, Light-Overload Use (PlD)":"355 kW","Output Current, Light-Overload Use (IlD)":"483 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039326-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039326-D/alternatives.json"},"ai":{"faq":[{"question":"What is 3ABD00039326-D's frame size?","answer":"Frame size R10."},{"question":"What is the input voltage and frequency range?","answer":"380-500 V 3-phase, 47.5-63 Hz."},{"question":"What are the output power ratings?","answer":"Normal use: 355 kW / 503 A. Heavy-duty: 250 kW / 361 A. Light-overload: 355 kW / 483 A."},{"question":"What is the enclosure protection?","answer":"IP20, open type — for indoor cabinet installation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039326-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039326-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}