{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039366-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039366-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039366-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039366-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 series, LV AC industrial single drive module, 400 kW / 725 A normal use, frame size R11, IP20, 380-415 V 3-phase input.","salesMarkdown":"## What this drive module delivers Heavy-duty use is rated 315 kW / 566 A, and light-overload use 400 kW / 715 A — so you pick the duty class that matches your load profile, not just the headline number. Frame size R11 tells the cabinet planner the physical envelope and bus-bar layout. This is a three-phase module accepting 380-415 V input at 47.5-63 Hz, so it covers 50 Hz and 60 Hz grids without reconfiguration. IP20 protection means it mounts inside an enclosure — no washdown rating, no outdoor exposure. The open-type NEMA classification confirms it needs a clean, dry cabinet with proper clearance for airflow and arc flash containment. ## Duty ratings — which one governs your load The 725 A normal-use rating (400 kW) fits centrifugal pumps, fans, and general conveyors where overload is light and infrequent. Heavy-duty at 566 A (315 kW) is the figure for extruders, crushers, or hoists that demand sustained torque at low speed. Light-overload at 715 A (400 kW) sits between them — useful for applications with occasional peak demand but not continuous hard duty. A common mistake is sizing on the normal-use number alone. If your motor draws 600 A during a start cycle that lasts 60 seconds, the heavy-duty curve is the one that keeps the module out of thermal trip. The datasheet's overload profile (not shown here) would confirm the exact time-current boundary. ## Cabinet integration notes Frame R11 drives the mounting footprint and bus-bar centers. Verify the cabinet depth allows for the DC-link bus bars and the optional braking chopper if your application needs dynamic braking. The IP20 enclosure means no gland plate sealing — route cables through the cabinet's own entry points and maintain separation between power and control wiring per the installation manual.","metaTitle":"ABB 3ABD00039366-D ACS880-04 Drive Module, 400 kW, 725 A, Fr","metaDescription":"ABB ACS880-04 LV AC industrial single drive module. 400 kW normal use, 725 A output. Frame size R11, IP20, 380-415 V 3-phase. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"400 kW","Output Current, Normal Use (In)":"725 A","Output Power, Heavy-Duty Use (PhD)":"315 kW","Output Current, Heavy-Duty Use (IhD)":"566 A","Output Power, Light-Overload Use (PlD)":"400 kW","Output Current, Light-Overload Use (IlD)":"715 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039366-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039366-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"Frame size R11. This determines the physical dimensions, bus-bar layout, and mounting hole pattern for cabinet integration."},{"question":"What input voltage and frequency does this module accept?","answer":"Three-phase input at 380-415 V, 47.5-63 Hz. This covers both 50 Hz and 60 Hz grids without hardware changes."},{"question":"What are the key output ratings I should use for sizing?","answer":"Normal use: 400 kW / 725 A. Heavy-duty use: 315 kW / 566 A. Light-overload use: 400 kW / 715 A. Select the duty class matching your load profile — the heavy-duty figure governs for demanding applications like crushers or hoists."},{"question":"What compliance documentation is available for this part?","answer":"The module carries IEC classification (Pn 400 kW, 725 A) per the product description. It is classified under WEEE Category 4 (Large Equipment). For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of conformity with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039366-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039366-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}