{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039381-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039381-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039381-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039381-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 LV AC single drive module, 3ABD00039381-D, 630 kW / 880 A normal use, 380-500 V 3-phase, IP20, frame size R11.","salesMarkdown":"## Drive module for high-power motor control The ABB 3ABD00039381-D is an LV AC industrial single drive module rated for 630 kW normal-use output at 880 A, with heavy-duty capability at 500 kW / 697 A and light-overload at 560 kW / 857 A. It accepts 380-500 V three-phase input across 47.5-63 Hz and is enclosed to IP20 in frame size R11. ## Rating selection for duty cycle Three output ratings let you match the module to the load profile. Normal-use 880 A covers continuous constant-torque applications. Heavy-duty 697 A applies for high-starting-torque or cyclic loads where the drive must deliver peak current without tripping. Light-overload 857 A sits between — useful for pumps and fans with moderate transient demand. Frame R11 is an open-type module (NEMA Open Type) for cabinet mounting. IP20 allows direct access to terminals inside a locked enclosure. Frequency tolerance 47.5-63 Hz handles weak mains or generator supply.","metaTitle":"ABB 3ABD00039381-D ACS880-04 Drive Module, 880 A, 630 kW","metaDescription":"ABB 3ABD00039381-D ACS880-04 LV AC drive module, 630 kW normal use, 880 A output, 380-500 V, 3-phase, IP20, frame R11. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"630 kW","Output Current, Normal Use (In)":"880 A","Output Power, Heavy-Duty Use (PhD)":"500 kW","Output Current, Heavy-Duty Use (IhD)":"697 A","Output Power, Light-Overload Use (PlD)":"560 kW","Output Current, Light-Overload Use (IlD)":"857 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039381-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039381-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"Frame size R11. This is a large cabinet-mount module; the open-type NEMA enclosure requires installation in a suitable electrical enclosure."},{"question":"What are the output ratings for normal, heavy-duty, and light-overload use?","answer":"Normal use: 630 kW / 880 A. Heavy-duty: 500 kW / 697 A. Light-overload: 560 kW / 857 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039381-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039381-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}