{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039382-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039382-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039382-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039382-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB 3ABD00039382-D, ACS880-04 series, LV AC industrial single drive module, frame size R11, 315 kW / 585 A normal use, IP20, 3-phase 380-415 V input.","salesMarkdown":"It's rated for 315 kW normal-use output at 585 A, with heavy-duty capability at 250 kW / 429 A and light-overload at 315 kW / 575 A. Input is 3-phase 380-415 V, 47.5-63 Hz. IP20 open-type enclosure — plan for cabinet mounting with adequate cooling. Light-overload at 575 A (IlD) splits the difference for applications with moderate overload profiles. IE2 efficiency class means it meets the base EU efficiency level — not premium, but compliant for most installations where the motor itself drives the system efficiency. IP20 open-type enclosure — no integral touch protection on the power terminals, so it's intended for a locked cabinet or electrical room. Frame R11 is a standard ABB drive module footprint; verify cabinet depth and busbar layout against the mechanical drawing. WEEE Category 4 (large equipment) applies for end-of-life disposal tracking. No UL listing stated in the spec record — confirm with the factory if UL 508C or CSA is required for your jurisdiction.","metaTitle":"ABB 3ABD00039382-D ACS880-04 Drive Module, 315 kW, 585 A","metaDescription":"ABB 3ABD00039382-D LV AC drive module, 315 kW normal use, 585 A output, IP20, frame R11. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"315 kW","Output Current, Normal Use (In)":"585 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"429 A","Output Power, Light-Overload Use (PlD)":"315 kW","Output Current, Light-Overload Use (IlD)":"575 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039382-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039382-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size for 3ABD00039382-D?","answer":"Frame size R11. This is a standard ABB drive module frame; confirm mechanical dimensions against the cabinet layout before ordering."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039382-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039382-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}