{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039388-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039388-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039388-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039388-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 LV AC industrial single drive module, 3ABD00039388-D, frame R11, 560 kW / 820 A normal use, 380-500 V, IP20.","salesMarkdown":"Input accepts 380 to 500 V at 47.5 to 63 Hz, covering 50/60 Hz mains globally. The normal-use (light-overload) rating of 560 kW / 820 A suits variable-torque applications — pumps, fans, compressors — where peak demand stays under 110 % of rated current. Heavy-duty use at 450 kW / 625 A applies for constant-torque or high-starting-torque loads; the 820 A normal-use figure is the one to match against the motor nameplate for most process applications. Frame R11 is the mechanical envelope for this power class; verify cabinet depth and busbar spacing against the ACS880-04 installation manual. ## Mounting and protection Open-type enclosure with IP20 protection — suitable for installation inside a clean, dry cabinet. The module mounts on a backplate or DIN rail per the frame R11 footprint. All power and control terminations are accessible from the front; maintain clearance above and below for airflow as specified in the drive manual.","metaTitle":"ABB 3ABD00039388-D ACS880-04 Drive Module, 820 A, 560 kW","metaDescription":"ABB ACS880-04 single drive module, 560 kW normal-use, 820 A output, 380-500 V, IP20, frame R11. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"560 kW","Output Current, Normal Use (In)":"820 A","Output Power, Heavy-Duty Use (PhD)":"450 kW","Output Current, Heavy-Duty Use (IhD)":"625 A","Output Power, Light-Overload Use (PlD)":"560 kW","Output Current, Light-Overload Use (IlD)":"807 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039388-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039388-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of 3ABD00039388-D?","answer":"Normal-use output is 560 kW at 820 A; heavy-duty output is 450 kW at 625 A. Input voltage range is 380–500 V at 47.5–63 Hz. Frame size is R11."},{"question":"What is the frame size of 3ABD00039388-D?","answer":"Frame R11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039388-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039388-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}