{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039404-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039404-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039404-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039404-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 drive module, 3ABD00039404-D, R11 frame, 560 kW / 820 A normal use, 380-500 V 3-phase, IP20.","salesMarkdown":"## Drive module for high-power motor control It accepts 380–500 V three-phase input across 47.5–63 Hz, covering both 50 Hz and 60 Hz grids globally. The R11 frame size determines cabinet cutout and busbar layout, so verify mechanical fit before specifying. ## Duty ratings and real-world motor sizing Three overload profiles are defined. Normal use (Pn) delivers 560 kW continuous at 820 A; heavy-duty use (PhD) derates to 450 kW at 625 A for high-torque or constant-torque loads like conveyors or extruders. Light-overload use (PlD) matches normal-use power at 560 kW but with 807 A output current, a slight reduction from the full 820 A rating. For a 560 kW motor on a pump or fan, the normal-use figure is the sizing target. For a crusher or mixer, use the heavy-duty column to avoid nuisance trips. The open-type NEMA enclosure classification reinforces this: the drive relies on the panel's enclosure for personnel protection. Plan for forced-air cooling or cabinet ventilation to manage heat dissipation at 820 A continuous output.","metaTitle":"ABB 3ABD00039404-D ACS880-04 Drive Module, 560 kW, 820 A","metaDescription":"ABB 3ABD00039404-D ACS880-04 drive module, R11 frame, 560 kW normal use at 820 A, 380-500 V 3-phase input, IP20, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"560 kW","Output Current, Normal Use (In)":"820 A","Output Power, Heavy-Duty Use (PhD)":"450 kW","Output Current, Heavy-Duty Use (IhD)":"625 A","Output Power, Light-Overload Use (PlD)":"560 kW","Output Current, Light-Overload Use (IlD)":"807 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039404-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039404-D/alternatives.json"},"ai":{"faq":[{"question":"What frame size is 3ABD00039404-D?","answer":"The frame size is R11. This determines the physical mounting dimensions and busbar connections for cabinet integration."},{"question":"What are the normal-use and heavy-duty power ratings?","answer":"Normal-use output is 560 kW at 820 A. Heavy-duty output is 450 kW at 625 A for constant-torque or high-starting-torque applications."},{"question":"What is the IP rating and enclosure type?","answer":"IP20 protection and NEMA Open Type. The module must be mounted inside a suitable cabinet for environmental and personnel protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039404-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039404-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}