{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039406-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039406-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039406-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039406-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-04 LV AC industrial single drive module, Frame R11, 380-415 V 3-phase, 315 kW / 585 A normal use, 250 kW / 429 A heavy duty, IP20, IE2.","salesMarkdown":"It delivers 315 kW output power at 585 A in normal use, with a heavy-duty rating of 250 kW at 429 A for tougher loads. Input is 380-415 V three-phase, 47.5-63 Hz, and the unit carries an IE2 efficiency level. Frame size is R11, enclosure is IP20 Open Type — it's meant for a panel, not standalone. ## Sizing and duty The normal-use rating (315 kW, 585 A) covers continuous motor operation at full load. Heavy-duty use (250 kW, 429 A) applies when the drive sees overload cycles — conveyors, crushers, pumps with high starting torque. Light-overload use (315 kW, 575 A) sits close to normal but with a slightly different current curve. Pick the duty class that matches your load profile; the heavy-duty number is the one that keeps the drive alive on a tough line. Frame R11 is a cabinet-mount module, IP20 rated — no external weatherproofing. Open Type NEMA enclosure means it needs a clean, dry panel environment. Three-phase input at 380-415 V, frequency range 47.5-63 Hz covers 50/60 Hz grids. The 585 A normal-use current dictates busbar and cable sizing; plan for adequate copper cross-section and ventilation around the heat sink.","metaTitle":"ABB 3ABD00039406-D ACS880-04 Drive Module, 315 kW, 585 A","metaDescription":"ABB ACS880-04 LV AC single drive module, 315 kW / 585 A normal use, 250 kW / 429 A heavy duty. Frame R11, IP20, 380-415 V 3-phase. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R11","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"315 kW","Output Current, Normal Use (In)":"585 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"429 A","Output Power, Light-Overload Use (PlD)":"315 kW","Output Current, Light-Overload Use (IlD)":"575 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039406-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039406-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"Frame size is R11."},{"question":"What are the key power ratings for normal and heavy-duty use?","answer":"Normal use: 315 kW at 585 A. Heavy-duty use: 250 kW at 429 A. Light-overload use: 315 kW at 575 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039406-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039406-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}