{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00039784-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00039784-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00039784-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00039784-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-01 series, 3ABD00039784-D, wall-mounted LV AC drive, 75 kW normal duty, 145 A output, 380–415 V 3-phase, IP55, NEMA 12, frame R6.","salesMarkdown":"Heavy-duty use (PhD) drops to 55 kW at 105 A, which is the rating you size against for constant-torque or high-starting-torque applications such as conveyors or extruders. Light-overload use (PlD) matches the normal-duty current at 138 A, so the drive can handle occasional overloads up to that level without tripping. Pick the duty cycle that matches your load profile; the heavy-duty number is the one that governs if you're pushing a demanding mechanical load. Wall-mounted, frame R6. The WEEE category 4 classification (any external dimension over 50 cm) confirms it's a large piece of gear; plan for a dedicated lifting point during installation. No DIN-rail option here — it bolts directly to the wall or a backplate. This is a current-production variant, so you can spec it into a BOM without worrying about a PCN in the next cycle.","metaTitle":"ABB 3ABD00039784-D ACS880-01 Drive, 75 kW, 145 A","metaDescription":"ABB ACS880-01 wall-mounted drive, 75 kW normal duty, 145 A output, 380-415 V 3-phase, IP55, NEMA 12, IE2, frame R6. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00039784-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00039784-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of the 3ABD00039784-D?","answer":"Frame size R6."},{"question":"What is the input frequency range for this drive?","answer":"47.5 to 63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00039784-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00039784-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}