{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00045248","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00045248","canonicalUrl":"https://aoctrl.com/abb/3ABD00045248","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00045248","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380 series, LV AC machinery drive module, 3ABD00045248, 1.5 kW normal use, 4 A output, 380-480 V input, IP20, IE2, frame size R1.","salesMarkdown":"The ABB 3ABD00045248 is an LV AC machinery drive module rated for 1.5 kW normal-use output at 4 A, fed from a 380-480 V three-phase supply. Frame size R1 keeps the panel footprint compact for this power class. Efficiency lands at IE2. Normal-use output (Pn) is 1.5 kW at 4 A — that is the continuous rating for a standard variable-torque load like a fan or pump. Heavy-duty use (PhD) drops to 1.1 kW at 3.3 A, which is the rating to use for constant-torque applications such as conveyors or positive-displacement pumps where the motor pulls rated current across the speed range. Light-overload use (PlD) stays at 1.5 kW but current is 3.8 A, reflecting a slightly different thermal model for intermittent overload profiles. Pick the duty column that matches your machine's torque demand, not the highest number. IP20 enclosure suits a clean, dry cabinet. Open Type NEMA rating aligns with that: install inside a panel that provides the environmental seal.","metaTitle":"ABB 3ABD00045248 ACS380 Drive Module, 1.5 kW, 4 A","metaDescription":"ABB ACS380-040C-04A0-4+K469 LV AC machinery drive module, 1.5 kW normal use, 4 A output, 380-480 V input, IP20, IE2. Active production. Frame size R1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"4 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"3.3 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Output Current, Light-Overload Use (IlD)":"3.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00045248","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00045248/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive module?","answer":"Frame size R1."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal use: 1.5 kW at 4 A. Heavy-duty use: 1.1 kW at 3.3 A."},{"question":"What input voltage and frequency does it accept?","answer":"380-480 V three-phase, 47.5-63 Hz."},{"question":"What is the efficiency level and enclosure protection?","answer":"IE2 efficiency, IP20 enclosure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00045248","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00045248 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}