{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00045678-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00045678-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00045678-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00045678-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-073A-4+B056, 3ABD00045678-D, LV AC general-purpose wall-mounted drive, 37 kW / 73 A, IP55, NEMA 12, Frame R4.","salesMarkdown":"It operates on a 3-phase 380–500 V input, 47.5–63 Hz, and is enclosed to IP55 / NEMA 12. Frame size R4. Three duty ratings are listed: normal use (Pn 37 kW, In 73 A), heavy-duty use (PhD 30 kW, IhD 61 A), and light-overload use (PlD 37 kW, IlD 68.4 A). For a pump or fan with a quadratic torque curve, the normal-use figure governs selection. For a constant-torque load like a conveyor or extruder, the heavy-duty rating is the one that determines headroom — 30 kW / 61 A is the continuous limit under that duty class. The light-overload rating sits between the two, at 68.4 A, and is useful when the load profile has occasional peaks but stays below the normal-use current.","metaTitle":"ABB 3ABD00045678-D ACS580-01-073A-4+B056, 37 kW, 73 A, IP55","metaDescription":"ABB 3ABD00045678-D is an active LV AC general-purpose wall-mounted drive, 37 kW normal use, 73 A output, IP55, NEMA 12. Frame size R4. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Phases":"3-phase","Mounting":"Wall Mount","Frequency":"47.5 ... 63 Hz","IP Rating":"IP55","Frame Size":"R4","Output Power":"37 kW","Input Voltage":"380 ... 500 V","Output Current":"73 A","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00045678-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00045678-D/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00045678-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00045678-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}