{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00045704-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00045704-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00045704-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00045704-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted drive, 3ABD00045704-D, 75 kW normal-use output, 145 A, IP55, NEMA 12, frame size R6.","salesMarkdown":"The ABB 3ABD00045704-D is an ACH580-01 wall-mounted LV AC drive rated 75 kW normal-use output at 145 A, with a heavy-duty rating of 55 kW at 105 A for demanding loads like conveyors or compressors that need sustained torque at low speed. The 380–500 V three-phase input covers standard global industrial voltages, and the 47.5–63 Hz frequency range means it handles 50 Hz and 60 Hz mains without derating. The IP55 enclosure with NEMA Type 12 rating suits it for washdown areas and dusty environments — think HVAC plant rooms, pump stations, or light industrial floors where hose-down cleaning is routine. Wall-mount it directly; no separate cabinet needed for most indoor locations.","metaTitle":"ABB 3ABD00045704-D ACH580-01 Drive, 75 kW, 145 A, IP55, R6","metaDescription":"ABB ACH580-01 3ABD00045704-D LV AC wall-mounted drive, 75 kW normal use, 145 A output, IP55, NEMA 12, IE2. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00045704-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00045704-D/alternatives.json"},"ai":{"faq":[{"question":"What are the normal-use and heavy-duty ratings for this drive?","answer":"Normal use is 75 kW at 145 A output; heavy-duty use is 55 kW at 105 A. The heavy-duty rating provides higher overload capability for constant-torque loads."},{"question":"What enclosure protection does 3ABD00045704-D have?","answer":"IP55 with NEMA Type 12 — suitable for indoor environments with dust, dirt, and hose-down cleaning. Wall-mountable without an additional enclosure."},{"question":"What is the frame size of this drive?","answer":"Frame size R6. Confirm the mounting dimensions against your panel layout before ordering."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00045704-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00045704-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}