{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00045727-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00045727-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00045727-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00045727-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01-145A-4+B056, wall-mounted LV AC drive, 75 kW / 145 A normal use, IP55, NEMA Type12, IE2, frame size R6.","salesMarkdown":"The ABB 3ABD00045727-D is an ACQ580-01-145A-4+B056, a wall-mounted LV AC drive built for water and wastewater duty. Input voltage range is 380 to 500 V three-phase, and it handles line frequencies from 47.5 to 63 Hz — so it works on 50 or 60 Hz systems without a hiccup. Enclosure is IP55 with a NEMA Type12 rating, meaning it's sealed against dust and hose-down water — fine for pump stations or treatment plants where the air's damp and dirty. Frame size is R6, which tells you the physical footprint and cooling requirements for panel layout. ## Efficiency and duty ratings This drive carries an IE2 efficiency level. That's the baseline for the class — it won't win any energy awards, but it's the standard fit for most industrial water applications where the motor's already sized for the load. The normal-use (light-overload) output is 75 kW at 138 A, while the heavy-duty curve drops to 55 kW at 105 A. If you're running a centrifugal pump that rarely hits full torque, the normal-use rating is your number. For a positive-displacement pump or a conveyor with frequent starts, the heavy-duty rating is the one that keeps the drive out of thermal trouble.","metaTitle":"ABB 3ABD00045727-D ACQ580-01-145A-4+B056, 75 kW, 145 A, IP55","metaDescription":"Active ABB ACQ580-01-145A-4+B056 wall-mounted drive, 75 kW normal use, 145 A, IP55, NEMA Type12, IE2. Frame size R6. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00045727-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00045727-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00045727-D?","answer":"Frame size is R6. That's the physical mounting footprint for this wall-mounted drive."},{"question":"What enclosure protection does this drive have?","answer":"IP55 and NEMA Type12. It's dust-tight and protected against hose-down water, suitable for damp or washdown environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00045727-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00045727-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}