{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00045729-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00045729-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00045729-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00045729-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 series, LV AC wall-mounted drive, 3ABD00045729-D, 110 kW / 206 A normal duty, IP55, NEMA Type12, Frame R7.","salesMarkdown":"Input accepts 380–500 V three-phase, 47.5–63 Hz. IP55 and NEMA Type12 rating means it handles hose-down washdown and dust — typical for pump rooms and treatment plants. Wall-mounted, R7 frame. No floor stand needed; plan for a reinforced backplate and clearance for the top cable entry.","metaTitle":"ABB 3ABD00045729-D ACQ580-01 LV Drive, 110 kW, 206 A, IP55","metaDescription":"ABB ACQ580-01 LV AC wall-mounted drive, 110 kW normal-use output, 206 A, IP55, NEMA 12. Active production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R7","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP55","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"206 A","Output Power, Heavy-Duty Use (PhD)":"90 kW","Output Current, Heavy-Duty Use (IhD)":"169 A","Output Power, Light-Overload Use (PlD)":"110 kW","Output Current, Light-Overload Use (IlD)":"196 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00045729-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00045729-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 110 kW at 206 A; heavy-duty output is 90 kW at 169 A. Input voltage is 380–500 V three-phase, 47.5–63 Hz. Enclosure is IP55 / NEMA Type12, wall-mounted, frame R7."},{"question":"What is the frame size of 3ABD00045729-D?","answer":"Frame size is R7."},{"question":"What is the input frequency range?","answer":"47.5–63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00045729-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00045729-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}