{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046051-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046051-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00046051-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046051-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 LV AC HVAC drive, 3ABD00046051-D, 75 kW / 145 A normal use, 380-500 V, 3-phase, IP21, NEMA 1, IE2, frame size R6.","salesMarkdown":"It delivers 75 kW normal-use output at 145 A from a 380–500 V three-phase supply, with a heavy-duty rating of 55 kW / 105 A for tougher fan or pump profiles. The drive carries IE2 efficiency and is enclosed to IP21 with a NEMA Type 1 rating — suitable for indoor installation where dust and dripping water are controlled. Three current ratings are listed: 145 A for normal use (Pn 75 kW), 138 A for light-overload use (PlD 75 kW), and 105 A for heavy-duty use (PhD 55 kW). The normal and light-overload figures share the same power because the current difference reflects the thermal margin for constant-torque vs variable-torque loads. Wall-mounted, frame size R6. The IP21 / NEMA 1 enclosure means it is drip-proof but not hose-down rated — keep it in a clean electrical room or a ventilated cabinet. The WEEE category is 4 (Large Equipment), which affects end-of-life disposal planning in EU markets.","metaTitle":"ABB 3ABD00046051-D ACH580-01 HVAC Drive, 75 kW, 145 A","metaDescription":"Active ABB ACH580-01 LV AC drive, 75 kW normal use, 145 A, 380-500 V, 3-phase, IP21, NEMA 1, IE2. Frame size R6. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046051-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046051-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R6."},{"question":"What is the input frequency range?","answer":"47.5 to 63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046051-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046051-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}