{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046052-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046052-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00046052-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046052-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted LV AC drive, 3-phase, 380–500 V input, 90 kW / 169 A normal-use output, IP21, Frame R6, IE2.","salesMarkdown":"## Sizing for the load Normal-use 169 A suits variable-torque HVAC fans and centrifugal pumps. Light-overload rating at 161 A splits the difference for cyclic loads. Pick the duty column that matches your motor nameplate and application profile. Wall-mount, IP21 / NEMA Type 1. R6 frame. Plan for top and bottom cable entry clearance. Ambient temperature derating applies above 40 °C — check the drive's thermal curve. No gland plate included; order separately if needed. ## Sourcing posture Active, current lifecycle stage. No last-time-buy window or successor announced. Frame R6 is a common size; if a swap is urgent, the heavy-duty current column (145 A) is the conservative fit for an unknown load.","metaTitle":"ABB 3ABD00046052-D ACH580-01 Drive, 90 kW, 169 A, IP21, R6","metaDescription":"Active-production ABB ACH580-01 wall-mount drive. 90 kW normal use, 169 A output, 380-500 V input, IP21, IE2 efficiency. Frame R6. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"90 kW","Output Current, Normal Use (In)":"169 A","Output Power, Heavy-Duty Use (PhD)":"75 kW","Output Current, Heavy-Duty Use (IhD)":"145 A","Output Power, Light-Overload Use (PlD)":"90 kW","Output Current, Light-Overload Use (IlD)":"161 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046052-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046052-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size?","answer":"Frame R6. That determines the mounting footprint, cable entry dimensions, and available option slots."},{"question":"What is the closest alternative in the same family?","answer":"If you need a direct swap, the ACH580-01 in the same frame R6 with matching voltage and current ratings is the obvious candidate. For a different duty profile, step up or down one current tier within the R6 frame family — verify the heavy-duty column against your motor full-load amps."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046052-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046052-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}