{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046057-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046057-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00046057-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046057-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted LV AC drive, 3ABD00046057-D, 200 kW normal-use output at 430 A, 380-500 V 3-phase input, 47.5-63 Hz, IP21, frame size R9.","salesMarkdown":"## What this drive delivers The ABB 3ABD00046057-D is an ACH580-01 wall-mounted LV AC drive rated 200 kW normal-use output at 430 A, with heavy-duty output also at 200 kW but 363 A — meaning the drive handles the same power across duty classes, but the current derating to 363 A under heavy-duty use reflects the higher sustained torque demand typical of HVAC fan and pump loads. Input accepts 380-500 V three-phase across 47.5-63 Hz, covering the global 50/60 Hz mains standard. IE2 efficiency level keeps line losses manageable for continuous fan and pump duty. IP21 enclosure with Type 1 NEMA rating suits indoor electrical rooms and mechanical spaces where condensation is controlled — not for washdown zones or outdoor weather exposure. Wall-mounted, frame size R9 — this is a large drive. Plan for adequate wall support and clearance for the IP21 enclosure's cooling airflow. The WEEE Category 4 classification (any external dimension >50 cm) confirms the physical footprint exceeds half a meter in at least one axis.","metaTitle":"ABB 3ABD00046057-D ACH580-01 VFD, 200 kW, 430 A, IP21","metaDescription":"ABB 3ABD00046057-D ACH580-01 wall-mounted VFD. 200 kW normal-use output, 430 A, 380-500 V 3-phase input. Active production, IE2 efficiency. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"Frame Size":"R9","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"200 kW","Output Current, Normal Use (In)":"430 A","Output Power, Heavy-Duty Use (PhD)":"200 kW","Output Current, Heavy-Duty Use (IhD)":"363 A","Output Power, Light-Overload Use (PlD)":"200 kW","Output Current, Light-Overload Use (IlD)":"400 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046057-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046057-D/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size and mounting for 3ABD00046057-D?","answer":"Frame size R9, wall-mounted. The IP21 enclosure is Type 1 NEMA rated for indoor use."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046057-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046057-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}