{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046070-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046070-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00046070-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046070-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-04 LV AC drive module, 3ABD00046070-D, 355 kW / 650 A normal use, 380-480 V, 3-phase, IP00, IE2, R10 frame, cabinet-built.","salesMarkdown":"The ABB 3ABD00046070-D is an ACH580-04 LV AC drive module for HVAC duty, rated 355 kW normal-use output at 650 A (380-480 V, 3-phase). Heavy-duty use drops to 250 kW / 477 A; light-overload use holds at 355 kW / 634 A. Efficiency is IE2, which is the baseline for this power class. The IP00 open-type enclosure (NEMA Open) means it's intended for cabinet-built installation — no onboard weather protection, so it lives inside a panel or drive cubicle with forced ventilation. The R10 frame size matches the mechanical footprint for this power tier; cabinet cutouts and busbar spacing should follow the ACH580-04 installation manual for that frame. Input frequency range is 47.5 to 63 Hz, covering 50 Hz and 60 Hz grids without derating. The WEEE Category 4 classification (Large Equipment) means end-of-life disposal follows the EU WEEE directive for units over 50 cm in any dimension — factor that into your site's environmental compliance plan.","metaTitle":"ABB 3ABD00046070-D ACH580-04 Drive, 355 kW, 650 A, R10 Frame","metaDescription":"ABB 3ABD00046070-D LV AC drive module for HVAC, 355 kW / 650 A normal use, 380-480 V, IP00, IE2, R10 frame. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"3ABD00046070-D","Frame Size":"R10","description":"LV AC drive module for HVAC, IEC: Pn 355 kW, 650 A (ACH580-04-650A-4)","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP00","Output Power, Normal Use (Pn)":"355 kW","Output Current, Normal Use (In)":"650 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"477 A","Output Power, Light-Overload Use (PlD)":"355 kW","Output Current, Light-Overload Use (IlD)":"634 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7b73c58f2571ece1ac0aa66004864ca8.pdf","sourceUrl":"https://www.abb.com/global/en/products/3abd00046070-d"},"ai":{"faq":[{"question":"What is 3ABD00046070-D's listed frame size (R10) on this component line?","answer":"The frame size is R10. That determines the mechanical mounting footprint, busbar spacing, and cabinet cutout dimensions for the ACH580-04 series at this power level."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046070-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046070-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}