{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046198","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046198","canonicalUrl":"https://aoctrl.com/abb/3ABD00046198","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046198","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380 machinery drive module, 3ABD00046198, R4 frame, 380-480 V 3-phase, 15 kW / 32 A normal duty, IP20, active production.","salesMarkdown":"The light-overload rating at 15 kW / 30.5 A is effectively the same as normal duty here; the real distinction is between the 32 A and 25 A current limits. If your motor plate says 30 A FLA, the normal-duty 32 A gives you headroom; if you need sustained overload capability, size to the 25 A heavy-duty line. Frame size R4 dictates a specific DIN-rail or backplate footprint — verify the mounting hole pattern against your cabinet layout before cutting the gland plate. The 47.5-63 Hz input frequency range covers 50/60 Hz grids globally, but the drive's DC bus capacitors are sized for that range; running below 47.5 Hz on the AC input side isn't supported.","metaTitle":"ABB 3ABD00046198 ACS380 drive module, 15 kW, 32 A, R4","metaDescription":"ABB ACS380-040C-032A-4+K454 machinery drive, 15 kW normal duty / 32 A, 380-480 V 3-phase, IP20, R4 frame. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R4","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"32 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"25 A","Output Power, Light-Overload Use (PlD)":"15 kW","Output Current, Light-Overload Use (IlD)":"30.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046198","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046198/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00046198?","answer":"The frame size is R4, which determines the physical mounting dimensions and footprint for cabinet layout."},{"question":"What are the normal-duty and heavy-duty power ratings?","answer":"Normal-duty output is 15 kW at 32 A; heavy-duty output is 11 kW at 25 A. Light-overload rating is 15 kW at 30.5 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046198","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046198 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}