{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046356","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046356","canonicalUrl":"https://aoctrl.com/abb/3ABD00046356","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046356","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH531-01-09A4-4, LV AC wall-mounted drive, 4 kW, 9.4 A, 380-480 V, IP20, Frame R0.","salesMarkdown":"The ABB 3ABD00046356 is an ACH531-01-09A4-4 LV AC wall-mounted drive for HVAC applications, rated 4 kW normal-use output at 9.4 A, with a light-overload rating of 4 kW at 8.9 A. Input is 380-480 V three-phase, 47.5-63 Hz. Frame size R0, IP20 open type enclosure. The 9.4 A normal-use output current is the figure to size branch protection and cabling for continuous motor duty. Standby loss of 15 W is modest — the drive won't heat up a small cabinet when idling, but it's not zero; factor it into the ventilation calc if the panel is tight. Frame size R0 is the smallest in this wall-mount family. IP20 enclosure for clean, dry indoor environments. Open-type NEMA rating. Maximum ambient 40 °C. IE2 efficiency class is the baseline for this generation of drive. Not the highest tier available today, but adequate for standard HVAC fan and pump loads where premium efficiency isn't specified.","metaTitle":"ABB 3ABD00046356 ACH531-01-09A4-4, 4 kW, 9.4 A","metaDescription":"ABB ACH531-01-09A4-4 LV AC wall-mounted drive, 4 kW, 9.4 A, 380-480 V, IP20, frame R0. Active production. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R0","Standby Loss":"15 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"Product Not in WEEE Scope","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"6.5 kV·A","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Light-Overload Use (PlD)":"4 kW","Output Current, Light-Overload Use (IlD)":"8.9 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046356","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046356/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00046356?","answer":"Frame size R0 — the smallest in the ACH531 wall-mount family."},{"question":"What is the standby loss of this drive?","answer":"15 W standby loss. Modest, but not zero — account for it in cabinet thermal calculations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046356","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046356 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}