{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046357","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046357","canonicalUrl":"https://aoctrl.com/abb/3ABD00046357","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046357","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH531-01-12A6-4, LV AC wall-mounted HVAC drive, 5.5 kW, 12.6 A, 380–480 V 3-phase, IP20, Frame Size B1.","salesMarkdown":"The ABB 3ABD00046357 is an ACH531-01-12A6-4 LV AC wall-mounted drive built for HVAC fan and pump duty. Rated 5.5 kW normal-use output at 12.6 A, it runs on 380–480 V three-phase mains at 47.5–63 Hz. The IE2 efficiency level and IP20 open-type enclosure suit panel-mount installations where ambient stays at or below 40 °C. The 5.5 kW / 12.6 A normal-use rating (In) is the continuous motor capacity — match it to a 5.5 kW induction fan or pump for full nameplate headroom. Light-overload duty (PlD) stays at 5.5 kW with 12 A output, so there is no extra burst capacity for conveyors or compressors; this drive is specced for variable-torque HVAC loads, not constant-torque machinery. The 8.7 kV·A apparent power output confirms the transformer sizing for the drive's input stage. Frame size B1 determines the physical envelope for panel layout and gland plate planning. Standby loss of 16 W adds to the cabinet heat budget — account for it when sizing ventilation or cooling, especially in a multi-drive enclosure.","metaTitle":"ABB 3ABD00046357 ACH531 HVAC Drive, 5.5 kW, 12.6 A","metaDescription":"ABB ACH531-01-12A6-4 LV AC wall-mounted HVAC drive, 5.5 kW / 12.6 A normal use, 380–480 V 3-phase, IP20, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"B1","Standby Loss":"16 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"Product Not in WEEE Scope","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"8.7 kV·A","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"12.6 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Output Current, Light-Overload Use (IlD)":"12 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046357","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046357/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00046357?","answer":"Frame size B1. This determines the mounting footprint and gland plate layout for panel integration."},{"question":"What is the standby loss of this drive?","answer":"Standby loss is 16 W. Include this in the cabinet heat load calculation when sizing ventilation or cooling."},{"question":"What are the key output ratings?","answer":"Normal-use output is 5.5 kW at 12.6 A. Light-overload output is also 5.5 kW at 12 A. Apparent power output is 8.7 kV·A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046357","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046357 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}