{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046362","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046362","canonicalUrl":"https://aoctrl.com/abb/3ABD00046362","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046362","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH531-01-046A-4, 3ABD00046362, LV AC wall-mounted HVAC drive, 22 kW / 46 A normal use, 380-480 V, IP20, R3 frame.","salesMarkdown":"The ABB ACH531-01-046A-4 (3ABD00046362) is a low-voltage AC wall-mounted drive for HVAC applications, rated for 22 kW normal-use output at 46 A and 31.0 kVA apparent power. It runs on 380-480 V three-phase, 47.5-63 Hz, and is built into an R3 frame with IP20 protection. Standby loss is 16 W. Mounts as a wall-mounted module (R3 frame). Input voltage range 380-480 V three-phase. Normal-use output is 46 A at 22 kW; light-overload rating is 42.8 A at 22 kW. IP20 enclosure. Ambient ceiling is 40 °C. Efficiency class IE2 — meets the base level for variable-speed drives in most regions. Standby loss of 16 W is what it pulls when the motor is stopped but the control electronics stay live; factor that into panel heat budget if the drive idles for long periods.","metaTitle":"ABB ACH531-01-046A-4 3ABD00046362 Drive, 22 kW, 46 A","metaDescription":"ABB ACH531-01-046A-4 LV AC wall-mounted HVAC drive, 22 kW normal use, 46 A output, IP20, R3 frame. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R3","Standby Loss":"16 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"Product Not in WEEE Scope","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"31.0 kV·A","Output Power, Normal Use (Pn)":"22 kW","Output Current, Normal Use (In)":"46 A","Output Power, Light-Overload Use (PlD)":"22 kW","Output Current, Light-Overload Use (IlD)":"42.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046362","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046362/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00046362?","answer":"The frame size is R3."},{"question":"What is the standby loss of 3ABD00046362?","answer":"Standby loss is 16 W."},{"question":"What are the key output ratings of 3ABD00046362?","answer":"Normal-use output is 22 kW at 46 A; light-overload output is 22 kW at 42.8 A. Apparent power output is 31.0 kVA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046362","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046362 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}