{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046369","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046369","canonicalUrl":"https://aoctrl.com/abb/3ABD00046369","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046369","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH531-01-206A-4 LV AC wall-mounted drive, 110 kW, 206 A, 380-480 V, 3-phase, IP20, Frame R7.","salesMarkdown":"The ABB 3ABD00046369 is an ACH531-01-206A-4 LV AC wall-mounted drive built for HVAC duty. It delivers 110 kW normal-use output at 206 A, fed from a 380-480 V 3-phase supply with a 47.5 to 63 Hz frequency range. Frame size R7 keeps it wall-mountable for tight mechanical rooms. The 110 kW normal-use power rating and 206 A output current are the numbers that decide if this drive matches your motor. Light-overload duty is rated at 110 kW and 196 A, so it handles continuous fan or pump loads without headroom for short-term spikes. Standby loss of 36 W matters for panel thermal budgeting — that's heat that stays in the enclosure when the drive is idle, not negligible in a sealed cabinet at 40 °C ambient. Efficiency is IE2, which is the baseline for this class — not premium, but expected for HVAC drives where full-load hours are moderate. The IP20 enclosure and NEMA Open Type mean it's for indoor installation only; no washdown or dust-tight rating. HVAC drives like this one go on fans, pumps, and compressors in commercial buildings and industrial ventilation. The wall-mount frame R7 and 110 kW output suit medium-to-large air handlers or chiller pumps. No fieldbus or I/O expansion is listed in this base variant — it's a straightforward VFD for fixed-speed replacement or variable-torque retrofits.","metaTitle":"ABB 3ABD00046369 ACH531 Drive, 110 kW 206 A, Frame R7","metaDescription":"Active ABB ACH531-01-206A-4 LV AC wall-mounted drive, 110 kW normal use output, 206 A, 380-480 V 3-phase, IP20, frame R7. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R7","Standby Loss":"36 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"Product Not in WEEE Scope","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"143.0 kV·A","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"206 A","Output Power, Light-Overload Use (PlD)":"110 kW","Output Current, Light-Overload Use (IlD)":"196 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046369","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046369/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00046369?","answer":"Frame size R7, which is a wall-mountable form factor for the ACH531 series."},{"question":"What is the standby loss of 3ABD00046369?","answer":"Standby loss is 36 W — that's the heat dissipated when the drive is powered but not running a motor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046369","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046369 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}