{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046373","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046373","canonicalUrl":"https://aoctrl.com/abb/3ABD00046373","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046373","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH531-01 LV AC wall-mounted HVAC drive, IEC, 250 kW, 430 A, 3-phase, 380-480 V, IP20, Frame R9.","salesMarkdown":"The ABB 3ABD00046373 is an ACH531-01 LV AC wall-mounted drive built for HVAC duty, rated 250 kW normal-use output at 430 A on a 380-480 V three-phase supply. Frame size R9, IP20 enclosure, open type NEMA. Efficiency class IE2, standby loss 80 W. Frequency range 47.5 to 63 Hz covers 50/60 Hz grids. Ambient temperature max 40 °C.","metaTitle":"ABB 3ABD00046373 ACH531-01 HVAC Drive, 250 kW, 430 A","metaDescription":"ABB ACH531-01 LV AC wall-mounted HVAC drive, 250 kW, 430 A, IP20, 380-480 V, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R9","Standby Loss":"80 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"Product Not in WEEE Scope","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"298.0 kV·A","Output Power, Normal Use (Pn)":"250 kW","Output Current, Normal Use (In)":"430 A","Output Power, Light-Overload Use (PlD)":"200 kW","Output Current, Light-Overload Use (IlD)":"400 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046373","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046373/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R9."},{"question":"What is the standby loss?","answer":"80 W."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046373","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046373 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}