{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046435","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046435","canonicalUrl":"https://aoctrl.com/abb/3ABD00046435","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046435","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS380-040C-12A6-4+L538, LV AC machinery drive, 5.5 kW, 12.6 A, 380-480 V, 3-phase, IP20, Frame R2.","salesMarkdown":"The 3ABD00046435 is an ABB ACS380 series LV AC machinery drive, order code ACS380-040C-12A6-4+L538. It's rated for 5.5 kW normal-use output at 12.6 A, with a heavy-duty rating of 4 kW at 9.4 A. Input is 380-480 V three-phase, 47.5-63 Hz, and the enclosure is IP20 open type, Frame R2. Normal-use current of 12.6 A is the number to match against your motor's full-load amps for constant-torque applications. The heavy-duty rating of 9.4 A covers variable-torque loads like pumps and fans where you need headroom for overload. IE2 efficiency class means it meets the base EU efficiency level for motor drives — no premium-efficiency premium, but compliant for standard industrial lines. Frame R2 is the physical footprint — mounts as a module, IP20, so it's panel-mount only, no washdown or dust tolerance. Open-type NEMA enclosure confirms it needs a clean, dry electrical room.","metaTitle":"3ABD00046435 ACS380 Drive, 5.5 kW, 12.6 A, Frame R2","metaDescription":"Active-production LV AC machinery drive, 3ABD00046435, 5.5 kW normal use, 12.6 A, 380-480 V, 3-phase, IP20, Frame R2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"12.6 A","Output Power, Heavy-Duty Use (PhD)":"4 kW","Output Current, Heavy-Duty Use (IhD)":"9.4 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Output Current, Light-Overload Use (IlD)":"12 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046435","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046435/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3ABD00046435?","answer":"Frame R2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046435","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046435 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}