{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3ABD00046702-D","brand":"ABB","brandSlug":"abb","productSlug":"3ABD00046702-D","canonicalUrl":"https://aoctrl.com/abb/3ABD00046702-D","factsUrl":"https://aoctrl.com/api/mcp/products/3ABD00046702-D","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 general purpose wall-mounted drive, 3ABD00046702-D, 380-480 V 3-phase, 75 kW / 145 A normal duty, IP21, NEMA 1, IE2, frame R6.","salesMarkdown":"## Drive selection summary Order code 3ABD00046702-D is a wall-mounted VFD rated 75 kW normal duty at 145 A output on a 380-480 V 3-phase supply. Heavy-duty use drops to 55 kW and 105 A. Light-overload use is rated 75 kW at 138 A. Frame size is R6. Efficiency is IE2 class. No broker or surplus channel is needed for this active ABB catalog item. ## Duty ratings in practice The normal-use rating of 75 kW at 145 A applies to variable-torque loads such as centrifugal pumps and fans. For constant-torque loads — mixers, extruders, positive-displacement pumps — the heavy-duty rating of 55 kW at 105 A governs. The light-overload rating of 138 A sits between the two, providing a margin for applications with occasional overload events.","metaTitle":"3ABD00046702-D ACS580-01-145A-4+B056+X1582, 75 kW 145 A","metaDescription":"Active ABB ACS580-01 wall-mounted drive, 380-480 V 3-phase, 75 kW normal duty, 145 A output, IP21, NEMA 1, IE2 efficiency, frame R6. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R6","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3abd00046702-d","alternativesUrl":"https://aoctrl.com/api/mcp/products/3ABD00046702-D/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal duty: 75 kW at 145 A. Heavy-duty: 55 kW at 105 A. Input: 380-480 V 3-phase, 47.5-63 Hz. Enclosure: IP21 / NEMA Type 1. Frame size R6. Efficiency: IE2."},{"question":"What frame size is 3ABD00046702-D?","answer":"The drive is frame size R6, which determines the mounting dimensions, cable entry locations, and enclosure volume for this 75 kW / 145 A output class."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3ABD00046702-D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3ABD00046702-D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}